U1 - 12, U1 - 19 – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 402

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-12

(004B) Drive Status

Int Ctl Sts 1

Verifies the drive operation status.

U1 - 12=

00000000

During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection

1

1

1

1
1

1

1
1

No signal output

available

U1-13

(004E)

Terminal A1 Input

Level

Term A1 Level

Displays the signal level to analog input terminal A1.

10 V: 100%

0.1%

U1-14

(004F)

Terminal A2 Input

Level

Term A2 Level

Displays the signal level to analog input terminal A2.

10 V: 100%

0.1%

U1-15

(0050)

Terminal A3 Input

Level

Term A3 Level

Displays the signal level to analog input terminal A3.

10 V: 100%

0.1%

U1-16

(0053)

Output Frequency after

Soft Starter

SFS Output

Displays output frequency with ramp time and S-curves. Units

determined by o1-03.

10 V: Max

frequency

0.01 Hz

U1-18

(0061)

oPE Fault Parameter

OPE Error Code

Displays the parameter number that caused the oPE02 operation

error.

No signal output

available

U1-19

(0066)

MEMOBUS/Modbus

Error Code

Transmit Err

Displays the contents of a MEMOBUS/Modbus error.

U1 - 19=

00000000

CRC Error
Data Length Error
Not Used

Parity Error
Overrun Error
Framing Error

Timed Out

Not Used

1

1

0

1

1

1

1

0

No signal output

available

U1-24

(007D) Input Pulse Monitor

Term RP Inp Freq

Displays the frequency to pulse train input terminal RP.

Determined by

H6-02

1 Hz

U1-25

(004D)

Software Number

(Flash)

CPU 1 SW Number

FLASH ID

No signal output

available

U1-26

(005B) Software No. (ROM)

CPU 2 SW Number

ROM ID

No signal output

available

U1-29

(07AA) Software No. (PWM)

CPU 3 SW Number

PWM ID

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

U1-75

(0851)

Time-Hour/Minute

Time Hr Min HHMM Displays the current time (Hours and Minutes).

No signal output

available

U1-76

(0852)

Date – Year

Date Year

Displays the current year.

No signal output

available

U1-77

(0853)

Date – Month/Day

Date Mo Day MMDD Displays the current date (Month and Date).

No signal output

available

U1-78

(0854)

Date – Week Day

Date Week

Displays the current day of the week.

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

No signal output

available

U1-79

(0B9A)

<5>

PI Feedback Back-up

PI Fdbk Backup

Displays the PI Feedback Back-up signal (H3-oo = 24) used

when the primary PI Feedback (H3-oo = B) is lost.

No signal output

available

dep. on

P1-02

B.15 U: Monitors

402

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising