Changing Parameter Settings or Values

This example explains changing C1-02 (Deceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.

Note:

During serial communication writing, if a parameter change is also attempted via the HOA keypad, a “BUSY - WRITE PROTECTED”

message will display. Parameter change will not be possible from the HOA keypad until an Enter command is received via the serial

communication to finish the serial writing process.

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U5-99= 0.0PSI
U1-02= 0.00Hz

U1-91= 0.0PSI

DRV

Auto Setpoint

Rdy

<-MONITOR->

LSEQ

LREF

2. Press

or

until the Parameter Setting Mode screen appears.

Home

- MODE -

PRG

Programming

FWD

3. Press

to enter the parameter menu tree.

-PRMSET-

Initialization

Select Language

PRG

FWD

A

1-00= 0

Home

DATA

4. Press

or

to select the C parameter group.

-PRMSET-

Basic Setup

Accel Time 1

PRG

FWD

C

1-01=

20.0 sec

FWD

Home

DATA

5. Press

two times.

-PRMSET-

Accel/Decel

Accel Time 1

PRG

FWD

C

1

-01=

20.0 sec

-PRMSET-

C1-

01

= 20.0Sec

(0.0~6000.0)

“20.0 sec”

PRG

Accel Time 1

FWD

Home

Home

DATA

DATA

6. Press

or

to select parameter C1-02.

-PRMSET-

C1-

02

= 10.0Sec

(0.0~6000.0)

“10.0 sec”

PRG

Decel Time 1

FWD

Home

DATA

7. Press

to view the current setting value (10.0 s). The leftmost digit flashes.

-PRMSET-

C1-02=

0

010.0Sec

(0.0~6000.0)

“10.0 sec”

PRG

Decel Time 1

Home

FWD

8. Press

F2

or

until the desired number is selected. “1” flashes.

-PRMSET-

C1-02=00

1

0.0Sec

(0.0~6000.0)

“10.0 sec”

PRG

Decel Time 1

Home

FWD

9. Press

and enter 0020.0.

-PRMSET-

C1-02=00

2

0.0sec

(0.0~6000.0)

“10.0 sec”

PRG

Decel Time 1

Home

FWD

10. Press

to confirm the change.

Entry Accepted

11. The display automatically returns to the screen shown in Step 6.

-PRMSET-

C1-

02

= 10.0Sec

(0.0~6000.0)

“10.0 sec”

PRG

Decel Time 1

FWD

Home

DATA

4.3 Using the HOA Keypad