HOA Keypad Display

Fault Name

Low WL/SP Drive Disabled

Low Water Level / Suction Pressure Disabled
Water Level or Suction Pressure is below the Q4-06/Q5-06 setting.

Cause

Possible Solution

Drive is not allowed to run in MEMOBUS

multiplex when P9-51 is set to 1, the Water

Level or Suction Pressure is below the

Q4-06/Q5-06 setting, and the drive is

stopped or running as a lag drive.

• Confirm that the Water Level or Suction Pressure source is installed and working properly.
• Wait for the Water Level or Suction Pressure to recover.

HOA Keypad Display

Minor Fault Name

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and H2-oo =

10) are set.

Cause

Possible Solution

The cooling fan has reached 90% of its

expected performance life.

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

HOA Keypad Display

Minor Fault Name

LT-2

Capacitor Maintenance Time
The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solution

The main circuit and control circuit

capacitors have reached 90% of their

expected performance lives.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solution

The DC bus soft charge relay has reached

90% of expected performance life.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

LT-4

IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solution

IGBTs have reached 50% of their expected

performance life.

Check the load, carrier frequency, and output frequency.

HOA Keypad Display

Minor Fault Name

Main FdBk Lost

Using Backup FB

Main PI Feedback Lost

Cause

Possible Solution

Transducer failure

Confirm Main PI Feedback transducer is powered and operational.

Wire-break

Verify Main PI Feedback transducer connection to the drive.

HOA Keypad Display

Minor Fault Name

Net Flow Meter

Lost, Chk Source

Net Flow Meter Loss
There is no drive on the MEMOBUS network with an analog flow meter.

Cause

Possible Solution

5.3 Alarm Detection