Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 206

Advertising
background image

• Low Feedback / High Feedback Detection
• Not Maintaining Setpoint Detection
• Loss of Prime
• Low Flow / High Flow Detection
• Level Control / Suction Control / Vacuum Control
• Sleep Detection
• Sleep Boost

Forced De-Scale/De-Ragging Operation

When parameter P8-01 = 2 (Force De-scale), the drive will perform a De-scale/De-ragging operation every time it starts. This

mode is intended to be used during the setup of the De-scale/De-ragging function only.

Related Parameters, Multi-Function Digital Output Settings, and Alarms

No.

Parameter Name

Setting Values

P8-01

De-scale Operation Selection

Default: 0

Range: 0 to 2

P8-02

De-scale Cycle Count

Default: 1

Range: 1 to 100

P8-03

De-scale Frequency Reference

Default: 25.00 Hz

Range: 0.0 to 400.0

P8-04

De-scale Forward Run Time

Default: 10 s

Range: 1 to 6000

P8-05

De-scale Reverse Run Time

Default: 10 s

Range: 1 to 6000

P8-06

De-scale Acceleration Time

Default: 2.0 s

Range: 0.0 to 600.0

P8-07

De-scale Deceleration Time

Default: 2.0 s

Range: 0.0 to 600.0

P8-08

De-scale Pump Run Time

Default: 168.0 H

Range: 0.1 to 2000.0

H2 Multi-Function Digital Output Settings

H2-oo

Function

Description

A6

De-scale Active

Closed: De-scale is running

4.5 iQpump Presets and Functions

206

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising