Q5-03

(0F22) Suction Pressure

Setpoint

Suction Setpoint

Sets the amount of suction pressure to which the drive will

attempt to regulate.

Default: 20.0

<1>

Min.: 0.0

Max.: 1200.0

234

Q5-04

(0F23) Minimum Suction

Pressure

Min Suction Pres

Sets the level below which the suction pressure must fall for

longer than the Q5-05 time to put the drive to sleep and turn off

all lag pumps.

Default: 10.0

<1>

Min.: 0.0

Max.: 1200.0

Q5-05

(0F24) Suction Pressure Sleep

Delay Time

SP Sleep Dly Tm

Sets the length of time that the drive will delay after suction

pressure drops below the level set in Q5-04 before going to

sleep.

Default: 5 s

Min.: 0

Max.: 3600

Q5-06

(0F25) Wake-Up Suction

Pressure

Wake-Up Pres

Sets the level above which the suction pressure must rise for the

time set in Q5-07 for the drive to wake up when it has been put

to sleep via parameter Q5-04, Minimum Suction Pressure.

Default: 30.0

<1>

Min.: 0.0

Max.: 1200.0

234

Q5-07

(0F26)

Suction Pressure Sleep

Wake-Up Time

SP Wake-up Time

Sets the length of time for which the pressure must rise above

the level set in Q5-06 to wake up the drive when it has been put

to sleep via parameter Q5-04, Minimum Suction Pressure.

Default: 1 s

Min.: 0

Max.: 3600

Q5-08

(0F27)

Suction Pressure

Control Minimum

Speed

Suction Min Spd

Sets the minimum speed at which the drive will run when the

drive is controlling suction pressure.

When the drive is controlling outlet pressure or this parameter

is set lower than P1-06 and P4-12, parameters P1-06 and P4-12

will be used as the minimum speed.

Default: 0.00 Hz

Min.: 0.00

Max.: 400.00

Q5-09

(0F28) Low Suction Pressure

Detection Level

Low Pres Detect

Sets the level below which the suction pressure must fall for the

time set in Q5-10 to trigger a drive response according to Q5-11,

Low Suction Pressure Behavior Select.

Setting this parameter to 0.0 will disable the function.

Default: 0.0

<1>

Min.: 0.0

Max.: 1200.0

234

Q5-10

(0F29) Low Suction Pressure

Detection Time

Low Pres Det Tm

Sets the length of time that the suction pressure must fall below

the level set in Q5-09 to trigger a drive response according to

Q5-11, Low Suction Pressure Behavior Select.

Time unit is defined by Q5-18.

Default: 0.1

<2>

Min.: 0.0

Max.: 300.0

234

Q5-11

(0F2A)

Low Suction Pressure

Behavior Select

Low Pressure Sel

0: No Display

1: Alarm Only

2: Fault

3: Restart (Q5-15)

Determines drive response when the suction pressure drops

below the level set in Q5-09 for longer than the time set in

Q5-10.

0: No display (digital output only)

1: Alarm only

2: Fault

3: Auto-restart (time set by Q5-15)

Default: 1

Range: 0 to 3

235

Q5-12

(0F2B) High Suction Pressure

Detection Level

Hi Pres Detect

Sets the level above which the suction pressure must rise for the

time set in Q5-13 to trigger a drive response according to Q5-14.

Setting this parameter to 0.0 disables the function.

Default: 0.0

<1>

Min.: 0.0

Max.: 1200.0

Q5-13

(0F2C) High Suction Pressure

Detection Time

Hi Pres Det Tm

Sets the length of time that the suction pressure must rise above

the level set in Q5-12 to trigger a drive response according to

Q5-14.

Time unit is defined by Q5-18.

Default: 0.1

<2>

Min.: 0.0

Max.: 300.0

Q5-14

(0F2D)

High Suction Pressure

Behavior Select

Hi Pressure Sel

0: No Display

1: Alarm Only

2: Fault

3: Restart (Q5-15)

Determines drive response when the suction pressure rises

above the level set in Q5-12 for longer than the time set in Q5-13.

0: No display

1: Alarm only

2: Fault

3: Auto-restart (time set by Q5-15)

Default: 1

Range: 0 to 3

Q5-15

(0F2E)

Suction Pressure Auto-

Restart Time

Suction Restart

Sets the length of time that the drive will wait before attempting

an auto-restart of the Low Suction or High Suction fault.

Parameter is only effective when Q5-11 is set to 3 or Q5-14 is

set to 3 and L5-01 is greater than 0.

Default: 5.0 min

Min.: 0.1

Max.: 6000.0

Q5-16

(0F2F) Suction Control

Proportional Gain

Suction P Gain

Sets the proportional gain for the suction pressure control.

Default: 2.00

Min.: 0.00

Max.: 25.00

235

Q5-17

(0F30) Suction Control Integral

Time

Suction I Time

Sets the integral time for the suction pressure control.

Setting this parameter to 0.0 disables the suction pressure

control integrator.

Default: 5.0 s

Min.: 0.0

Max.: 360.0

235

Q5-18

(0F31)

Suction Pressure

Detection Time Unit

SuctionPresUnit

0: Minutes (min)

1: Seconds (sec)

Sets the time unit for Q5-10 and Q5-13.

0: Minutes (min)

1: Seconds (sec)

Default: 0

Range: 0, 1

B.12 Q: PID Controller Parameters