F6, F7: Communication Option Card

Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for DeviceNet and PROFIBUS-DP options. Other

parameters in the F6 group are used for communication-protocol-specific settings.

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F6-01

(03A2)

Communications Error

Operation Selection

Comm Bus Flt Sel

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-02

(03A3)

External Fault from

Comm. Option

Detection Selection

EF0 Detection

0: Always Detected

1: Only During Run

0: Always detected.

1: Detection during run only.

Default: 0

Range: 0, 1

F6-03

(03A4)

External Fault from

Comm. Option

Operation Selection

EF0 Fault Action

0: Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm Only

0: Ramp to stop. Decelerate to stop using the deceleration time

in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-04

(03A5)

bUS Error Detection

Time

BUS Err Det Time

Sets the delay time for error detection if a bus error occurs.

Default: 2.0 s

Min.: 0.0

Max.: 5.0

F6-07

(03A8)

Multi-Step Speed

Enable/Disable

Selection when NefRef/

ComRef is Selected

Fref PrioritySel

0: Net/Com REF

1: MultiStep Speed

0: Multi-step reference disabled

1: Multi-step reference enabled

Default: 0

Range: 0, 1

F6-08

(036A)

<1>

Reset Communication

Parameters

Com Prm Init Sel

0: Init Com Prms

1: No Init Com Prms

0: Reset all communication-related parameters (F6-oo) when

the drive is initialized using A1-03.

1: Communication-related parameters (F6-oo) are not reset

when the drive is initialized using A1-03.

Default: 0

Range: 0, 1

F6-30

(03CB)

PROFIBUS-DP Node

Address

PB Node Address

Sets the node address.

Default: 0

Min.: 0

Max.: 125

F6-31

(03CC)

PROFIBUS-DP Clear

Mode Selection

PB Clear Select

0: Reset to Zero

1: Hold Prev Value

0: Resets drive operation with a Clear mode command.

1: Maintains the previous operation state when Clear mode

command is given.

Default: 0

Range: 0, 1

F6-32

(03CD)

PROFIBUS-DP Data

Format Selection

PB Map Select

0: PPO Type

1: Conventional

0: PPO Type

1: Conventional

Default: 0

Range: 0, 1

F6-45

(02FB) BACnet Node Address BAC Node Address

Sets the node address.

Default: 1

Min.: 0

Max.: 127

F6-46

(02FC) BACnet Baud Rate

BAC Baud Rate

0: 93.75 kbps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19.2 kbps

5: 38.4 kbps

6: 57.6 kbps

7: 76.8 kbps

8: 115.2 kbps

0: 93.75 kbps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19.2 kbps

5: 38.4 kbps

6: 57.6 kbps

7: 76.8 kbps

8: 115.2 kbps

Default: 3

Range: 0 to 8

F6-47

(02FD) Rx to Tx Wait Time

Rx to Tx Wait T

Rx to Tx Wait Time

Default: 5 ms

Min.: 5

Max.: 65

F6-48

(02FE)

BACnet Device Objcet

ID 0

BAC Dev Obj Id 0

BACnet device object ID

Default: 0

Min.: 0

Max.: FFFF

F6-49

(02FF)

BACnet Device Objcet

ID 1

BAC Dev Obj Id 1

BACnet device object ID

Default: 0

Min.: 0

Max.: 3F

F6-50

(03C1)

DeviceNet MAC

Address

DN MAC Address

Selects the drive MAC address.

Default: 64

Min.: 0

Max.: 64

B.6 F: Options

344

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising