O3: copy function, O4: maintenance monitor settings – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 372

Advertising
background image

u

o3: Copy Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o3-01

(0515)

Copy Function

Selection

COPY SELECT

0: COPY SELECT

1: INV→OP READ

2: OP→INV WRITE

3: OP←→INV

VERIFY

0: No action

1: Read parameters from the drive, saving them onto the digital

operator.

2: Copy parameters from the digital operator, writing them to

the drive.

3: Verify parameter settings on the drive to check if they match

the data saved on the operator.

Default: 0

Range: 0 to 3

o3-02

(0516)

Copy Allowed Selection

Read Allowable

0: Disabled

1: Enabled

0: Read operation prohibited

1: Read operation allowed

Default: 1

Range: 0, 1

u

o4: Maintenance Monitor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o4-01

(050B)

Cumulative Operation

Time Setting

DrvElapsTimeCnt

Sets the value for the cumulative operation time of the drive in

units of 10 h.

Default: 0

Min.: 0

Max.: 9999

o4-02

(050C)

Cumulative Operation

Time Selection

ElapsTimeCntSet

0: Power-On Time

1: Running Time

0: Logs power-on time

1: Logs operation time when the drive output is active (output

operation time).

Default: 1

Range: 0, 1

o4-03

(050E)

Cooling Fan Operation

Time Setting

FanElapsTimeCn

Sets the value of the fan operation time monitor U4-03 in units

of 10 h.

Default: 0

Min.: 0

Max.: 9999

o4-05

(051D)

Capacitor Maintenance

Setting

BusCap Maint Set

Sets the value of the Maintenance Monitor for the capacitors.

See U4-05 to check when the capacitors may need to be

replaced.

Default: 0%

Min.: 0

Max.: 150

o4-07

(0523)

DC Bus Pre-Charge

Relay Maintenance

Setting

ChrgCircMaintSet

Sets the value of the Maintenance Monitor for the soft charge

bypass relay. See U4-06 to check when the bypass relay may

need to be replaced.

Default: 0%

Min.: 0

Max.: 150

o4-09

(0525)

IGBT Maintenance

Setting

IGBT Maint Set

Sets the value of the Maintenance Monitor for the IGBTs. See

U4-07 for IGBT replacement times.

Default: 0%

Min.: 0

Max.: 150

o4-11

(0510)

U2, U3 Initialization

Fault Data Init

0: No Reset

1: Reset

0: U2-oo and U3-oo monitor data is not reset when the drive

is initialized (A1-03).

1: U2-oo and U3-oo monitor data is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

o4-12

(0512)

kWh Monitor

Initialization

kWh Monitor Init

0: No Reset

1: Reset

0: U4-10 and U4-11 monitor data is not reset when the drive is

initialized (A1-03).

1: U4-10 and U4-11 monitor data is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

o4-13

(0528)

Number of Run

Commands Counter

Initialization

Run Counter Init

0: No Reset

1: Reset

0: Number of Run commands counter is not reset when the drive

is initialized (A1-03).

1: Number of Run commands counter is reset when the drive is

initialized (A1-03).

Default: 0

Range: 0, 1

o4-17

(3100)

Set/Reset Real-Time

Clock

Date/Time Config

0: — —

1: Set

2: Reset

Sets the current date and time for the Real-Time Clock.

0: - -

1: Set

2: Reset

Default: 0

Range: 0 to 2

160

o4-20

(081F) Time Display Format

Time Disp Format

0: 12-hour (AM/PM)

1: 24-hour

Sets the time display format.

0: 12-hour

1: 24-hour

Default: 0

Range: 0, 1

B.10 o: Operator-Related Settings

372

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising