B.10 o: Operator-Related Settings

The o parameters set up the HOA keypad displays.

u

o1: HOA Keypad Display Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o1-01

(0500)

Drive Mode Unit

Monitor Selection

User Monitor Sel

Selects the content of the last monitor that is shown when

scrolling through Drive Mode display. Enter the last three digits

of the monitor parameter number to be displayed: Uo-oo.

Default: 106

(Monitor U1-06)

Range: 104 to

699

o1-02

(0501)

User Monitor Selection

after Power Up

Power-On Monitor

1: Frequency Ref

2: FWD/REV

3: Output Freq

4: Output Current

5: User Monitor

1: Frequency reference (U1-01)

2: Direction

3: Output frequency (U1-02)

4: Output current (U1-03)

5: User-selected monitor (set by o1-01)

Default: 1

Range: 1 to 5

o1-03

(0502)

Digital Operator

Display Selection

Display Unit Sel

0: 0.01 Hz

1: 0.01%

2: r/min

3: User Units

Sets the units the drive should use to display the frequency

reference and motor speed monitors.

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of motor poles setting in

E2-04)

3: User-selected units (set by o1-09, o1-10 and o1-11)

Default: 0

Range: 0 to 3

o1-06

(0517)

User Monitor Selection

Mode

Monitor Mode Sel

0: 3 Mon Sequential

1: 3 Mon Selectable

Selects the monitors displayed on the second and third lines of

the digital operator display.

0: 3 Monitor Sequential (displays the next two sequential

monitors)

1: 3 Monitor Selectable (set by o1-07 and o1-08)

Default: 1

Range: 0, 1

o1-07

(0518)

Second Line Monitor

Selection

2nd Monitor Sel

Selects the monitor that is shown in the second line.

Enter the last three digits of the monitor parameter number to

be displayed: Uo-oo. For example, set "403" to display

monitor parameter U4-03.

Note:

Parameter is effective only

when o1-06 is set to 1.

Default: 102

Range: 101 to

699

o1-08

(0519)

Third Line Monitor

Selection

3rd Monitor Sel

Selects the monitor that is shown in the third line.

Enter the last three digits of the monitor parameter number to

be displayed: Uo-oo. For example, set "403" to display

monitor parameter U4-03.

Note:

Parameter is effective only

when o1-06 is set to 1.

Default: 191

Range: 101 to

699

o1-09

(051C)

Frequency Reference

Display Units

Fref Disp Unit

0: "WC:InchOfWater

1: PSI :lb/SqrInch

2: GPM:Gallons/Min

3: °F:DegFarenheit

4: CFM:Cubic ft/Min

5: CMH:Cubic m/Hr

6: LPH:Litres/Hr

7: LPS:Litres/Sec

8: Bar:Bar

9: Pa:Pascals

10: °C:DegCelsius

11: m: meters

12: ft: feet

13: LPM:Litres/Min

14: CMM:Cubic M/

Min

15: "Hg:Inch Mercury

24: Custom Unit

25: No Unit

Sets unit display for the frequency reference parameters and

frequency related monitors when o1-03 = 3.

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (inches of mercury)

24: Custom units (determined by o1-13 to o1-15)

25: None

Default: 25

Range: 0 to 15;

24, 25

o1-10

(0520)

User-Set Display Units

Maximum Value

UserDisp Scaling

These settings define the display values when o1-03 is set to 3.

o1-10 sets the display value that is equal to the maximum output

frequency.

o1-11 sets the position of the decimal position.

Default:

<1>

Range: 1 to

60000

o1-11

(0521)

User-Set Display Units

Decimal Display

UserDisp Dec

Default:

<1>

Range: 0 to 3

B.10 o: Operator-Related Settings

370