Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 436

Advertising
background image

Register No.

Contents

00CEH

Alarm Contents 8
bit 0

Temp Lost Geothermal Input (TLGI)

bit 1

Geo Params Chk Q2-05~Q2-08

bit 2

Time Not Set (TIM)

bit 3

Battery Low (bAT)

bit 4

Time Deviation Error (TdE)

bit 5

Setpoint Not Met (NMS)

bit 6

Emergency Override FWD (EoF)

bit 7

Emergency Override REV (Eor)

bit 8

bit 8 - Feedback Loss Go To B5-13

bit 9

bit 9 - Network Low WL/SP Drive Disabled

bit A

bit 10 - Analog Geo Temp Lost Switched to Net

bit B

High Suction (HISUC)

bit C

Water Lvl Loss (WLL)

bit D

SuctionPres Loss (SPL)

bit E, F

Reserved

00CFH

Reserved

00D0H

CPF Contents 1
bit 0, 1

Reserved

bit 2

A/D Conversion Error (CPF02)

bit 3

PWM Data Fault (CPF03)

bit 4, 5

Reserved

bit 6

EEPROM Memory Data Error (CPF06)

bit 7

Terminal Board Connection Error (CPF07)

bit 8

EEPROM Serial Communications Fault (CPF08)

bit 9, A

Reserved

bit B

RAM Fault (CPF11)

bit C

FLASH Memory Fault (CPF12)

bit D

Watchdog Circuit Exception (CPF13)

bit E

Control Circuit Fault (CPF14)

bit F

Reserved

00D1H

CPF Contents 2
bit 0

Clock Fault (CPF16)

bit 1

Timing Fault (CPF17)

bit 2

Control Circuit Fault (CPF18)

bit 3

Control Circuit Fault (CPF19)

bit 4

Hardware fault at power up (CPF20)

bit 5

Hardware fault at communication start up (CPF21)

bit 6

A/D Conversion Fault (CPF22)

bit 7

PWM Feedback Fault (CPF23)

bit 8

Drive Unit Signal Fault (CPF24)

bit 9

Terminal board is not properly connected. (CPF25)

bit A

ASIC BB Circuit Error (CPF26)

bit B

ASIC PWM Setting Register Error (CPF27)

bit C

ASIC PWM Pattern Error (CPF28)

bit D

ASIC On-delay Error (CPF29)

bit E

ASIC BBON Error (CPF30)

bit F

ASIC Code Error (CPF31)

C.9 MEMOBUS/Modbus Data Table