Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 243

Advertising
background image

HOA Keypad Display

Fault Name

CPF07 or

CPF08

Terminal Board Connection Error

Cause

Possible Solution

There is a faulty connection between the

terminal board and the control board

• Turn off the power and reconnect the terminal board.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF20 or CPF21

Control Circuit Error

Cause

Possible Solution

Hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF22

Hybrid IC Failure

Cause

Possible Solution

Hybrid IC failure on the power board

• Cycle power to the drive.
• If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the power board.

HOA Keypad Display

Fault Name

CPF23

Control Board Connection Error
Connection error between the control board and the drive

Cause

Possible Solution

Hardware is damaged

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

CPF25

Terminal Board Not Connected

Cause

Possible Solution

Terminal board is not connected correctly Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

HOA Keypad Display

Fault Name

CPF26 to CPF35

CPF40 to CPF43

Control Circuit Error
CPU error

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

E5

SI-T3 Watchdog Timer Error
The watchdog timed out.

Cause

Possible Solution

Data has not been received from the PLC Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and

proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.

5.2 Fault Detection

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

243

5

Troubleshooting