Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 178

Advertising
background image

No.

Parameter Name

Setting Values

Q2-06

Low Temperature to Run at Minimum Geothermal Speed

Default: 65.0 °F

Min.: -110.0

Max.: 275.0

Q2-07

High Temperature to Run at Minimum Geothermal Speed

Default: 75.0 °F

Min.: -110.0

Max.: 275.0

Q2-08

High Temperature to Run at Maximum Geothermal Speed

Default: 85.0 °F

Min.: -110.0

Max.: 275.0

Q2-09

Geothermal Temperature Loss Detection

Default: 1

Range: 0 to 2

Q2-10

Geothermal Sleep Delay Time

Default: 30 s

Min.: 0

Max.: 3600

Q2-11

Geothermal Temperature Delta Wake Level

Default: 0.0 °F

Min.: 0.0

Max.: 50.00

U1-99

Anti-No-Flow Timer

No signal output available

H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

Description

21

Geothermal Temperature

Full scale: Q2-02 = 10 V (or 20 mA), Q2-01 = 0 V (or 4 mA)

This input is internally limited to -999.9 °F to +999.9 °F

F

Not Used

Disables the functionality of the programmed terminal.

HOA Keypad Display

Error Name

oPE29

Geothermal Set Error

Cause

Possible Solutions

P1-01 parameter selection is not compatible

with Geothermal Mode (b1-01 = 5).

Confirm b1-01 and P1-01 parameter settings.

HOA Keypad Display

Fault Name

TLGI Geothermal Input

Temperature Lost Geothermal Input
The geothermal input is not present.

Cause

Possible Solutions

The input signal level has dropped below

3 mA or risen above 21 mA when the drive

was running and b1-01 = 5, H3-0o = 21

(Geothermal Input), H3-0o = 2

(4 to 20 mA), and Q2-09 = 2 (Fault).

Confirm that the device connected to the analog input terminal is installed and working properly.

The drive was running while b1-01 = 5,

H3-0o

≠ 21 (Geothermal Temp), and

Q2-09 = 2 (Fault).

Assign one of the analog inputs to “Geothermal Temperature”, H3-0o = 21.

HOA Keypad Display

Minor Fault Name

Geo Params

Chk Q2-05 to Q2-08

Geothermal Mode Parameters
The drive is running at the level set in Q2-03 due to an incorrect setting.

Cause

Possible Solution

The temperature parameter values are set

incorrectly.

Set the temperature parameters in the following order:

Q2-08 > Q2-07 > Q2-06 > Q2-05

4.5 iQpump Presets and Functions

178

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide