P6: flow meter setup – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 382

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P5-05

(0D30) HAND Reference 2

HAND Reference 2

Sets the frequency reference used when HAND Mode 2 is

active.

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

P5-06

(0D31) HAND Ref. 1 Loss of

Prime Level

HandRef1 LOP Lvl

Detects loss of prime in the pump.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P5-02, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

P5-07

(0D32) HAND Ref. 2 Loss of

Prime Level

HandRef2 LOP Lvl

Detects loss of prime in the pump.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

at the level set in P5-05, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<1>

Min.: 0.0

Max.: 1000.0

P5-09

(0D34)

HAND References Set

via Motor Operated Pot

Selection

HAND MOP Sel

0: Disabled

1: Enabled

Selects whether parameters P5-02 and P5-05 are changed via

MOP from the home screen.

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

<1> Unit text is set by P1-18, Prime Loss Detection Method.

u

P6: Flow Meter Setup

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P6-01

(0D5E) Flow Meter Scaling

Flow Meter Scale

When an analog input is used for the flow rate, this parameter

performs the following functions:
• Enables and disables flow meter functions. This parameter

must be set to a value greater than 0 to enable flow meter

functions.

• Sets the scaling for the “Flow Rate” analog input.
• Sets the scaling for the “Flow Rate” analog output.
• Sets the display scaling when “Flow Rate” is used as the PID

feedback.

When an pulse input is used for the flow rate, this parameter

performs the following functions:
• Enables and disables flow meter functions. Parameter must

be set to a value greater than zero to enable flow meter

functions.

• Sets the scaling for the “Flow Rate” analog output.
• Sets the display scaling when “Flow Rate” is used as the PID

feedback.

Default: 0.0

GPM

Min.: 0.0

Max.: 6000.0

P6-02

(0D5F) Turbine Input Scaling

(Course)

Turbine Scale 1

Sets the scaling for the turbine in pulses per gallon.

Pulses/Gallon = P6-02 + P6-03

This parameter is internally lower-limited to 0.0001 ppG.

Default: 1 ppG

Min.: 0

Max.: 6000

P6-03

(0D60) Turbine Input Scaling

(Fine)

Turbine Scale 2

Default: 0.0000

ppG

Min.: 0.0000

Max.: 0.9999

P6-04

(0D61) Water Flow Units

Water Flow Units

0: Gal/Min (GPM)

1: Gal/Hr (GPH)

2: Ft3/Min (CFM)

3: M3/Hr (CMH)

4: Acre-Ft/Yr (AFY)

Sets the display units for monitor U1-83, P2-02, P6-06, P6-17,

P9-41, and P9-42.

0: U.S. Gallons / min (GPM)

1: U.S. Gallons / hr (GPH)

2: Cubic Feet / min (CFM)

3: Cubic Meters / hr (CMH)

4: Acre-Feet / yr (AFY)

Default: 0

Range: 0 to 4

B.11 P: Pump Parameters

382