Setting 2220: 2-Wire Initialization

Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.

Setting 3330: 3-Wire Initialization

Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse

respectively.

Refer to Setting 0: 3-Wire Sequence on page

for more information on digital input functions.

S1

SN

FWD Run/Stop

2-Wire Control

Stop switch
(NC contact)

Operation switch
(NO contact)

S1

S2

SN

Run command
(Run on momentary close)

Stop command
(Stop on momentary open)

Sequence input common

3-Wire Control

Figure 4.27 2 & 3-Wire Control Wiring Examples

Notes on Parameter Initialization

The parameters shown in

Table 4.16

will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330.

Table 4.16 Parameters Not Changed by Drive Initialization

No.

Parameter Name

A1-00

Language Selection

E1-03

V/f Pattern Selection

F6-08

Communication Parameter Reset

L8-35

Installation Selection

o2-04

Drive/kVA Selection

Setting 5550: Terminal/Control Initialize

An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed

in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application

Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values

appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.

User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple

menus.

Refer to Pump Application Presets on page 169

for detailed information on Application Presets.

Setting 6008: Pressure Control

Application Preset for Pressure Control applications.

Refer to Pump Application Presets on page 169

for a list of parameters

and default values for this Application Preset.

Setting 6009: Pump Down Level

Application Preset for Pump Down Level applications.

Refer to Pump Application Presets on page 169

for a list of parameters

and default values for this Application Preset.

Setting 6010: Geothermal Mode

Application Preset for Geothermal Mode.

Refer to Pump Application Presets on page 169

for a list of parameters and default

values for this Application Preset.

Setting 6011: VTC Pressure Mode

Application Preset for VTC Pressure Mode.

Refer to Pump Application Presets on page 169

for a list of parameters and

default values for this Application Preset.

4.6 Basic iQpump Setup and Application Preset Parameters

208

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising