U4: maintenance monitors – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 406

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U3-38

(301C)

Time Hours and

Minutes at 6th Most

Recent Fault

Fault 6 HHMM

Displays the time when the sixth most recent fault occurred.

No signal output

available

U3-39

(301D)

Date Year at 7th Most

Recent Fault

Fault 7 YYYY

Displays the year when the seventh most recent fault occurred. No signal output

available

U3-40

(301E)

Date Month and Day at

7th Most Recent Fault

Fault 7 MMDD

Displays the date and day when the seventh most recent fault

occurred.

No signal output

available

U3-41

(301F)

Time Hours and

Minutes at 7th Most

Recent Fault

Fault 7 HHMM

Displays the time when the seventh most recent fault occurred. No signal output

available

U3-42

(3020)

Date Year at 8th Most

Recent Fault

Fault 8 YYYY

Displays the year when the eighth most recent fault occurred. No signal output

available

U3-43

(3021)

Date Month and Day

8th at Most Recent Fault Fault 8 MMDD

Displays the date and day when the eighth most recent fault

occurred.

No signal output

available

U3-44

(3022)

Time Hours and

Minutes at 8th Most

Recent Fault

Fault 8 HHMM

Displays the time when the eighth most recent fault occurred. No signal output

available

U3-45

(3023)

Date Year at 9th Most

Recent Fault

Fault 9 YYYY

Displays the year when the ninth most recent fault occurred.

No signal output

available

U3-46

(3024)

Date Month and Day at

9th Most Recent Fault

Fault 9 MMDD

Displays the date and day when the ninth most recent fault

occurred.

No signal output

available

U3-47

(3025)

Time Hours and

Minutes at 9th Most

Recent Fault

Fault 9 HHMM

Displays the time when the ninth most recent fault occurred.

No signal output

available

U3-48

(3026)

Date Year at 10th Most

Recent Fault

Fault 10 YYYY

Displays the year when the tenth most recent fault occurred.

No signal output

available

U3-49

(3027)

Date Month and Day at

10th Most Recent Fault Fault 10 MMDD

Displays the date and day when the tenth most recent fault

occurred.

No signal output

available

U3-50

(3028)

Time Hours and

Minutes at 10th Most

Recent

Fault 10 HHMM

Displays the time when the tenth most recent fault occurred.

No signal output

available

u

U4: Maintenance Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-01

(004C)

<1>

Cumulative Operation

Time

Drv Elapsed Time

Displays the cumulative operation time of the drive. The value

for the cumulative operation time counter can be reset in

parameter o4-01. Use parameter o4-02 to determine if the

operation time should start as soon as the power is switched on

or only while the Run command is present. The maximum

number displayed is 99999, after which the value is reset to 0.

No signal output

available

1 h

U4-02

(0075)

Number of Run

Commands

RUN Cmd Counter

Displays the number of times the Run command is entered.

Reset the number of Run commands using parameter o4-13.

This value will reset to 0 and start counting again after reaching

65535.

No signal output

available

1 Time

U4-03

(0067)

<2>

Cooling Fan Operation

Time

Fan Elapsed TIme

Displays the cumulative operation time of the cooling fan. The

default value for the fan operation time is reset in parameter

o4-03. This value will reset to 0 and start counting again after

reaching 99999.

No signal output

available

1 h

U4-04

(007E)

Cooling Fan

Maintenance

Fan Life Mon

Displays main cooling fan usage time as a percentage of its

expected performance life. Parameter o4-03 can be used to reset

this monitor.

Replace the fan when this monitor reaches 90%.

No signal output

available

1%

U4-05

(007C) Capacitor Maintenance Cap Life Mon

Displays main circuit capacitor usage time as a percentage of

their expected performance life. Parameter o4-05 can be used

to reset this monitor.

Replace the capacitor when this monitor reaches 90%.

No signal output

available

1%

B.15 U: Monitors

406

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide