Monitor data – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 428

Advertising
background image

u

Monitor Data

Monitor data can be read only.

Register No.

Contents

0020H

Drive Status 1
bit 0

During Run

bit 1

During Reverse

bit 2

Drive Ready

bit 3

Fault

bit 4

Data Setting Error

bit 5

Multi-Function Contact Output (terminal M1-M2)

bit 6

bit 7

bit 8 to bit D

Reserved

bit E

ComRef status

bit F

ComCtrl status

0021H

Fault Contents 1
bit 0

Overcurrent (oC), Ground fault (GF)

bit 1

Overvoltage (ov)

bit 2

Drive Overload (oL2)

bit 3

Overheat 1 (oH1), Drive Overheat Warning (oH2)

bit 4

Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)

bit 5

Reserved

bit 6

PID Feedback Loss (FbL / FbH)

bit 7

EF to EF8: External Fault

bit 8

CPFoo: Hardware Fault (includes oFx)

bit 9

Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/

UL4)

bit A

Reserved

bit B

Main Circuit Undervoltage (Uv)

bit C

Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)

bit D

Output Phase Loss (LF), Input Phase Loss (PF)

bit E

MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)

bit F

Operator Connection Fault (oPr)

0022H

Data Link Status
bit 0

Writing data or switching motors

bit 1

Reserved

bit 2
bit 3

Upper or lower limit error

bit 4

Data conformity error

bit 5

Writing to EEPROM

bit 6 to bit F

Reserved

0023H

Frequency Reference

<1>

0024H

Output Frequency

<1>

0025H

Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)

0026H

Output Current, 0.1 A units

0027H

Output Power

0028H

Reserved

C.9 MEMOBUS/Modbus Data Table

428

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising