H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

71

Secondary PI Feedback

Low

PI2 Feedback Low

Closed: PI2 feedback level is too low.

–

72

Secondary PI Feedback

High

PI2 FeedbackHigh

Closed: The PI2 feedback level is too high.

–

80

Pump 2 Control

Pump 2 Control

Contactor control for a second pump.

The function is active in contactor multiplex mode only (P1-01 = 1).

–

81

Pump 3 Control

Pump 3 Control

Contactor control for a third pump.

The function is active in contactor multiplex mode only (P1-01 = 1) and when

P3-01 is set to a value greater than 1.

–

82

Pump 4 Control

Pump 4 Control

Contactor control for a fourth pump.

The function is active in contactor multiplex mode only (P1-01 = 1) and when

P3-01 is set to a value greater than 2.

–

83

Pump 5 Control

Pump 5 Control

Contactor control for a fifth pump.

The function is active in contactor multiplex mode only (P1-01 = 1) and when

P3-01 is set to a value greater than 3.

–

84

Pump 6 Control

Pump 6 Control

Contactor control for a sixth pump.

The function is active in contactor multiplex mode only (P1-01 = 1) and when

P3-01 is set to a value greater than 4.

–

89

Output I Limit

Output I Lim

Closed: Drive output speed is being limited due to the output current limit or the

single phase foldback regulator.

–

8B

Lube Pump or Digital

Output Delay

Lube Pump or

DigitalOutput Delay

Closed: Refer to Lube Pump / Digital Output Delay parameters P4-30 and P4-31.

Display text is set by parameter P4-29.

–

8F

Internal Fan On

Internal Fan On

Internal Fan On

–

91

Pump Fault

Pump Fault

Closed when any of the following faults are active:
• Low feedback
• High feedback
• Low water
• High water
• NMS-Setpoint not met
• POC-Pump over cycle
• THMS-Thermostat input
• External pump fault

–

92

Transducer Loss

Transducer Loss

Closed: The analog output associated with PID feedback has risen above 21 mA

or fallen below 3 mA or a Transducer Loss alarm or fault is active.

–

93

Setptoint Not Met

SetPoint Not Met

Closed: During an “NMS-Setpoint Not Met” condition.

–

94

Loss of Prime

Loss of Prime

Closed: During an “LOP-Loss of Prime” condition.

–

95

Volute Thermostat Fault Volute-TStat Flt

Closed: Volute-Thermostat digital input is active.

–

96

High Feedback

High Feedback

Closed: During a “High Feedback” condition as defined by P1-11 and P1-12 OR

Closed: During a “High FB/Water” fault OR

Closed: During a “High Feedback” alarm

–

97

Low Feedback

Low Feedback

Closed: During a “Low Feedback” condition as defined by P1-08 and P1-12 OR

Closed: During a “Low FB/Water” fault OR

Closed: During a “Low Feedback” alarm

–

98

Low Flow

Low Flow

Closed: During the “Low Flow Fault” condition OR

Closed: During a Low Flow condition set by P6-06 to P6-08, including a “Low

Flow” alarm

–

99

Accum Level

Accum Level

Closed: Accumulated level has exceeded the P6-11 to P6-14 settings OR

Closed: During the “Accum Level” fault

–

9A

High Flow

High Flow

Closed: During the “High Flow Fault” condition OR

Closed: During a “High Flow” condition set by P6-17 and P6-18, including a “High

Flow” alarm

–

9B

Low Water Level

Low Water Level

Closed: The water level has dropped below the Low Detection Level set in Q4-09

for longer than the Low Level Detection Delay Time set in Q4-09 or if there is a

LOWWL – Low Water Level Fault.

–

9C

Low Suction

Low Suction

Closed: The suction pressure has dropped below the Low Suction Pressure

Detection Level set in Q5-09 for longer than the Low Suction Pressure Delay Time

set in Q5-10 or if there is a LOSUC – Low Suction Pressure Fault.

–

B.7 H Parameters: Multi-Function Terminals