Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 408

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-21

(07DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

1 = Reference 1 (b1-02)

Y: Input power supply data

0 = Digital operator

1 = External terminals

3 = MEMOBUS/Modbus communications

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, digital operator)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(07DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(07DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

U4-32

(07FB)

Motor Temperature

(NTC)

Motor Temperature

(NTC)

Displays the motor temperature (NTC).

U4-32 will display “20 °C” when a multi-function analog input

is not set for motor thermistor input (H1-oo = 17H). Monitor

is only present when a digital input is programmed for 17

(Thermistor Input).

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

200 °C

1 °C

U4-37

(1044)

oH Alarm Location

Monitor

OH Alarm Axis

Displays the module where the oH alarm occurred as a binary

number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

U4-38

(1045)

FAn Alarm Location

Monitor

FAN Alarm Axis

Displays the module where the FAn alarm occurred as a binary

number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

U4-39

(1046)

voF Alarm Location

Monitor

VOF Alarm Axis

Displays the module where the voF alarm occurred as a binary

number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

<1> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<2> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
<3> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

<4> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using

MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”

<5> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.

B.15 U: Monitors

408