Table – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 217

Advertising
background image

No.

Parameter Name

Setting

Range

Default

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

0 to 9F

81 (4)

<1>

: HAND Mode 2

H1-08

Multi-Function Digital Input Terminal S8 Function Selection

0 to 9F

F (6)

<1>

: Through Mode

<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).

Table 4.20 Multi-Function Digital Input Terminal Settings

Setting

Function

Page

0

3-Wire sequence

2

External Reference 1/2 Selection

3

Multi-Step Speed Reference 1

4

Multi-Step Speed Reference 2

5

Multi-Step Speed Reference 3

6

Jog reference selection

7

Accel/decel time selection 1

8

Baseblock command (N.O.)

9

Baseblock command (N.C.)

A

Accel/decel ramp hold

B

Drive overheat alarm (oH2)

C

Analog terminal input selection

F

Through mode

10

Up command

11

Down command

12

Forward Jog

13

Reverse Jog

14

Fault reset

15

Fast Stop (N.O.)

17

Fast Stop (N.C.)

18

Timer function input

19

PID disable

1A

Accel/decel time selection 2

1B

Program lockout

1E

Reference sample hold

20 to 2F Ext. pump fault

30

PID integral reset

31

PID integral hold

32

Multi-Step Speed

Reference 4

34

PID soft starter cancel

35

PID input level selection

40

Forward run command

(2-Wire sequence)

41

Reverse run command

(2-Wire sequence)

42

Run command

(2-Wire sequence 2)

43

FWD/REV command

(2-Wire sequence 2)

47

Node setup

Setting

Function

Page

51

Sequence Timer Disable

52

Sequence Timer Cancel

60

DC Injection Braking command

61

External Speed Search

command 1

62

External Speed Search

command 2

63

Field weakening

65

KEB Ride-Thru 1 (N.C.)

66

KEB Ride-Thru 1 (N.O.)

67

Communications test mode

68

High Slip Braking (HSB)

6A

Drive enable

73

Low City Press

75

Up 2 command

76

Down 2 command

7A

KEB Ride-Thru 2 (N.C.)

7B

KEB Ride-Thru 2 (N.O.)

80

HAND Mode

81

HAND Mode 2

83

Alternate Multi-Setpoint (Q1-02)

84

Alternate Multi-Setpoint (Q1-03)

85

Alternate Multi-Setpoint (Q1-04)

88

Volute-Thermostat Normally Open

89

Volute-Thermostat Normally Closed

8C

Disable Pre-Charge

8D

Multi Setpoint 1

8E

Multi Setpoint 2

8F

Low Water Level

90

High Water Level

92

Reset Accum

95

Remove Drive Disable

A8

Secondary PI Disable (N.O.)

A9

Secondary PI Disable (N.C.)

AA

Secondary PI Inverse Operation

AB

Secondary PI Integral Reset

AC

Secondary PI Integral Hold

AD

Select Secondary PI Parameters

AF

Emergency Override Forward Run

B0

Emergency Override Reverse Run

n

H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection

The drive has three multi-function output terminals.

Table 4.21

lists the functions available for theses terminals using H2-01,

H2-02, and H2-03.

4.6 Basic iQpump Setup and Application Preset Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

217