U5: pid monitors – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 409

Advertising
background image

u

U5: PID Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U5-01

(0057)

PID Feedback 1

PID Feedback 1

Displays the PID feedback value.

10 V: 100%

0.01%

<1>

U5-02

(0063)

PID Input

PID Input

Displays the amount of PID input (deviation between PID

setpoint and feedback).

10 V: 100%

0.01%

U5-03

(0064)

PID Output

PID Output

Displays PID control output.

10 V: 100%

0.01%

U5-04

(0065)

PID Setpoint

PID Setpoint

Displays the PID setpoint.

10 V: 100%

0.01%

<1>

U5-05

(07D2)

PID Differential

Feedback

PID Feedback 2

Displays the 2nd PID feedback value if differential feedback is

used (H3-oo = 16).

10 V: 100%

0.01%

U5-06

(07D3) PID Adjusted Feedback PID Diff Fdbk

Displays the difference of both feedback values if differential

feedback is used (U5-01 - U5-05). If differential feedback is not

used, then U5-01 and U5-06 will be the same.

10 V: 100%

0.01%

U5-14

(086B)

PI Output 2 Upper 4

Digits

PI Output2 U4

Displays the custom PI output.

U5-14 shows the upper 4 digits while U5-15 shows the lower 4

digits. Monitors are scaled by b5-43 and b5-44.

No signal output

available

1

<2>

U5-15

(086C)

PI Output 2 Lower 4

Digits

PI Output2 L4

Displays the custom PI output.

U5-14 shows the upper 4 digits while U5-15 shows the lower 4

digits. Monitors are scaled by b5-43 and b5-44.

No signal output

available

0.01

<2>

U5-17

(086E) PI2 Setpoint

PI2 Setpoint

Displays the secondary PI setpoint.

Dependent upon

S3-02

<3>

U5-18

(086F)

PI2 Feedback

PI2 Feedback

Displays the secondary PI feedback value.

Dependent upon

S3-02

<3>

U5-19

(0870)

PI2 Input

PI2 Input

Displays the secondary PI input (deviation between PI target

and feedback).

Dependent upon

S3-02

<3>

U5-20

(0871)

PI2 Output

PI2 Output

Displays the secondary PI control output.

Dependent upon

S3-02

<3>

U5-30

(3000)

Time Hr Min HHMM

Time Hr Min HHMM Displays the current time (Hours and Minutes).

No signal output

available

1

U5-31

(3001)

Date Year

Date Year

Displays the current year.

No signal output

available

1

U5-32

(3002)

Date Mo Day MMDD

Date Mo Day MMDD Displays the current date (Month and Day).

No signal output

available

1

U5-33

(3003)

Date Week 000W

Date Week

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

Displays the current date of the week.

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

No signal output

available

1

U5-99

(1599)

AUTO Setpoint

Auto Setpoint

Displays the PID Setpoint commanded by the source when the

drive is in AUTO Mode.

No signal output

available

0.01%

<1>

<1> Unit, range and resolution is determined by b5-20, b5-38, b5-39, and b5-46
<2> Unit is determined by b5-41
<3> Unit is determined by S3-04.

B.15 U: Monitors