Setting 0: Disabled

No communication error detection. The drive continues operation.

Setting 1: Enabled

If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and

the drive will operate as determined by parameter H5-04.

n

H5-06: Drive Transmit Wait Time

Sets the time the drive waits after receiving data from a master until responding data.

No.

Name

Setting Range

Default

H5-06

Drive Transmit Wait Time

5 to 65 ms

5 ms

Command message

Response message

Command message

PLC→Drive

PLC→Drive

Drive→PLC

Time

24 bit length H5-06 setting

Figure C.5 Drive Transmit Wait Time Setting

n

H5-07: RTS Control Selection

Enables or disables RTS control.

No.

Name

Setting Range

Default

H5-07

RTS Control Selection

0 or 1

1

Setting 0: Disabled. RTS is always on.

Use this setting with point-to-point RS-422 communications.

Setting 1: Enabled. RTS switches while sending.

Use this setting with RS-485 communications or when using multi-drop RS-422 communications.

n

H5-09: Communications Fault Detection Time

Sets the time the communications must be lost before the drive triggers a CE fault.

No.

Name

Setting Range

Default

H5-09

Communications Fault Detection Time

0.0 to 10.0 s

2.0 s

n

H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

No.

Name

Setting Range

Default

H5-10

Unit Selection for MEMOBUS/Modbus Register 0025H

0 or 1

0

Setting 0: 0.1 V units
Setting 1: 1 V units

C.4 MEMOBUS/Modbus Setup Parameters

418