Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 244

Advertising
background image

HOA Keypad Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the

PLC and F6-03 is set to a value other than

3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

HOA Keypad Display

Fault Name

EF1

Pump Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

Pump Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

Pump Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

Pump Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

Pump Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

Pump Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

Pump Fault (input terminal S7)
External fault at multi-function input terminal S7.

EF8

Pump Fault (input terminal S8)

External fault at multi-function input terminal S8.

Cause

Possible Solution

An external device tripped an alarm

function

Remove the cause of the external fault and reset the fault.

Wiring is incorrect

• Properly connect the signal lines to the terminals assigned for external fault detection

(H1-oo = 20 to 2B).

• Reconnect the signal line.

Multi-function contact input setting is

incorrect

• Check for unused terminals set for H1-oo = 20 to 2B (External Fault).
• Change the terminal settings.

HOA Keypad Display

Fault Name

Err

EEPROM Write Error
Data cannot be written to the EEPROM

Cause

Possible Solution

Noise has corrupted data while writing to

the EEPROM

• Press “ENTER” on the digital operator.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

FAn

Internal Fan Fault
Fan or magnetic contactor failure

Cause

Possible Solution

5.2 Fault Detection

244

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising