Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 306

Advertising
background image

u

Three-Phase 200 V Class Drive Models 2A0250 to 2A0415

Table A.3 Power Ratings Continued (Three-Phase 200 V Class)

Item

Specification

Drive Models

2A0250

2A0312

2A0360

2A0415

Maximum Applicable Motor Capacity (HP)

<1>

ND Rating

100

125

150

175

Input

Input Current (A)

<2>

ND Rating

271

324

394

471

Rated Voltage

Rated Frequency

Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc

<3>

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

ND Rating

124

148

180

215

Output

Rated Output Capacity (kVA)

<4>

ND Rating

<5>

95

119

137

158

Rated Output Current (A)

ND Rating

<5>

250

312

360

415

Overload Tolerance

ND Rating: 120% of rated output current for 60 s

(Derating may be required for applications that start and stop frequently)

Carrier Frequency

User-adjustable between 1 and 10 kHz

<5>

Maximum Output Voltage (V)

Three-phase 200 to 240 V (proportional to input voltage)

Maximum Output Frequency (Hz)

400 Hz (user-set)

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings

raise the carrier frequency and require current derating.

A.1 Power Ratings

306

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide