No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n3-04

(058B)

High-Slip Braking

Overload Time

HSB OL Time

V/f

V/f

Sets the time required for an HSB overload fault (oL7) to occur

when the drive output frequency does not change during an HSB

stop. This parameter does not typically require adjustment.

Default: 40 s

Min.: 30

Max.: 1200

n3-13

(0531)

Overexcitation

Deceleration Gain

Hflux Brake Gain

Sets the gain applied to the V/f pattern during Overexcitation

Deceleration (L3-04 = 4).

Default: 1.10

Min.: 1.00

Max.: 1.40

n3-14

(0532)

High Frequency

Injection during

Overexcitation

Deceleration

HarmInj@HiFlxBrk

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

n3-21

(0579)

High-Slip Suppression

Current Level

Hflux I Supp Lvl

Sets output current level at which the drive will start reducing

the overexcitation gain in order to prevent a too high motor slip

during Overexcitation Deceleration. Set as a percentage of the

drive rated current.

Default: 100%

Min.: 0

Max.: 150

n3-23

(057B)

Overexcitation

Operation Selection

Hflux Brake Sel

0: Enabled-Both Dir

1: Enabled-Fwd only

2: Enabled-Rev only

0: Enabled in both directions

1: Enabled only when rotating forward

2: Enabled only when in reverse

Default: 0

Range: 0 to 2

<1> Default setting is dependent on parameter L8-38, Frequency Reduction Selection.

u

n6: Online Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n6-01

(0570)

Online Tuning Selection

Online Tune Sel

0: Disabled

1: TerminalResAdj

2: VoltageAdjustm

OLV

OLV

OLV

OLV

0: Disabled

1: Line-to-line resistance tuning

2: Voltage correction. Setting not possible when Energy Saving

is enabled (b8-01).

Default: 0

Range: 0 to 2

n6-05

(05C7) Online Tuning Gain

R1 Comp Gain

OLV

OLV

OLV

OLV

Decrease this setting for motors with a relatively large rotor time

constant. If overload occurs, increase this setting slowly in

increments of 0.10.

Default: 1.0

Min.: 0.1

Max.: 50.0

B.9 n: Special Adjustment