b5-34

(019F) PID Output Lower Limit PID Out Low Lim

Sets the minimum output possible from the PID controller as a

percentage of the maximum output frequency.

Default: 0.00%

Min.: -100.00

Max.: 100.00

b5-35

(01A0) PID Input Limit

PID Input Limit

Limits the PID control input (deviation signal) as a percentage

of the maximum output frequency. Acts as a bipolar limit.

Default:

1000.0%

Min.: 0.0

Max.: 1000.0

b5-39

(01FF)

PID Setpoint Display

Digits

PID UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2: 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 1

Range: 0 to 3

215

b5-40

(017F)

Frequency Reference

Monitor Content during

PID

Fref Mon Sel@PID

0: Fref Mon w PID

1: Fref Mon w/o PID

0: Display the frequency reference (U1-01) after PID

compensation has been added.

1: Display the frequency reference (U1-01) before PID

compensation has been added.

Default: 0

Range: 0, 1

b5-41

(0160)

PI Output 2 Unit

Selection

PI Out2 Unit Sel

0: No Unit

1: PSI :lb/SqrInch

2: Pa:Pascals

3: Bar:Bar

4: "WC: InchOfWater

5: "Hg:Inch Mercury

6: ft: feet

7: m: meters

8: °F:DegFarenheit

9: °C:DegCelsius

10: %: Percent

25: Flow (use P6-04)

0: No Unit

1: Pounds per square inch

2: Pascals

3: Bar

4: Inch of Water

5: Inch of Mercury

6: Feet

7: Meters

8: Degrees Fahrenheit

9: Degrees Celsius

10: Percent

25: Flow (use P6-04)

Default: 0

Range: 0 to 10;

25

b5-42

(0161)

PI Output 2 Calculation

Mode

PI Out2 Calc Mode

0: Linear

1: Square root

2: 1/f2

3: 1/f3

0: Linear - the monitor displays PID output

1: Square root - the monitor displays square root PID output

2: Quadratic - the monitor displays 1/(PID output)

2

3: Cubic - the monitor displays 1/(PID output)

3

Note:

Used for U5-14 and U5-15 only.

Default: 0

Range: 0 to 3

b5-43

(0162)

PI Output 2 Monitor

Max Upper 4 Digits

PI Out2 MonMax U

Sets the upper 4 digits of the maximum monitor value.

Used with b5-44 to set maximum monitor value of U5-14 and

U5-15 at maximum frequency.

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 9999

b5-44

(0163)

PI Output 2 Monitor

Max Lower 4 Digits

PI Out2 MonMax L

Sets the lower 4 digits of the maximum monitor value.

Used with b5-43 to set maximum monitor value of U5-14 and

U5-15 at maximum frequency.

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 99.99

b5-45

(0164)

PI Output 2 Monitor

Minimum

PI Out2 MonMin

Sets the minimum display value at zero speed.

This function is effective when b5-42 is set to 0 (Linear output

mode).

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 999.9

b5-47

(017D)

Reverse Operation

Selection 2 by PID

Output

Output Rev Sel2

0: 0 Limit

1: Reverse

0: Zero limit when PID output is a negative value.

1: Reverse operation when PID output is a negative value

(Zero limit if the reverse operation is prohibited by b1-04).

Default: 1

Range: 0, 1

<1> Unit text is set by P1-18, Prime Loss Detection Method.
<2> Available in drive software versions PRG: 8551 and later.

B.2 b: Application

332