• When the “Disable Pre-Charge” digital input (H1-oo = 8C) is closed, even momentarily
• When the PID feedback satisfies Pre-charge level (P4-01):

Feedback is greater than Pre-Charge Level (P4-01) (forward-acting PID, b5-09 = 0)
Feedback is less than Pre-Charge Level (P4-01) (reverse-acting PID, b5-09 = 1)

• When the “Low Water” digital input (H1-oo = 8C) deactivates. A digital input must be programmed to “Low Water”

(H1-0o = 8F). The input is configured in P1-30 (0: normally open, 1: normally closed).

Related Parameters

No.

Parameter Name

Setting Values

P4-01

Pre-Charge Level

Default: 0.0 PSI

Min.: 0.0

Max.: 6000.0

P4-02

Pre-Charge Frequency

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

P4-03

Pre-Charge Time

Default: 0.0 min

Min.: 0.0

Max.: 3600.0

P4-05

Pre-Charge Loss of Prime Level

Default: 0.0 A

Min.: 0.0

Max.: 1000.0

P4-06

Pre-Charge Frequency 2

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

P4-07

Pre-Charge Time 2

Default: 0.0 min

Min.: 0.0

Max.: 3600.0

P4-08

Pre-Charge Loss of Prime Level 2

Default: 0.0 A

Min.: 0.0

Max.: 1000.0

H1 Multi-Function Digital Input Settings

H1-oo

Setting

Function

Description

8C

Disable Pre-Charge

Closed: Pre-Charge disabled.

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

Description

A4

Pre-Charge

Closed: Drive is in Pre-Charge mode.

R un

C omm an d

P re-C ha rge

Sing le speed – C om plete via tim er

“Pre-cha rge

Active”

M essage &

D igital Ou tpu t

(H 2-0x = A4)

Ou tpu t

F requen cy

P 4-03

Pre-cha rge T im e

P4-02 – Pre-cha rge F requen cy

P4-01 Pre-cha rge level = 0.0 AND P4-07 Pre-cha rge T im e 2 = 0.0 m in

PID N OT

disab led

Figure 4.16 Pre-Charge Single Speed Complete via Timer

4.5 iQpump Presets and Functions

192