U2: fault trace – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 404

Advertising
background image

u

U2: Fault Trace

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U2-01

(0080)

Current Fault

Current Fault

Displays the current fault.

No signal output

available

U2-02

(0081)

Previous Fault

Last Fault

Displays the previous fault.

No signal output

available

U2-03

(0082)

Frequency Reference at

Previous Fault

Frequency Ref

Displays the frequency reference at the previous fault.

No signal output

available

0.01 Hz

U2-04

(0083)

Output Frequency at

Previous Fault

Output Freq

Displays the output frequency at the previous fault.

No signal output

available

0.01 Hz

U2-05

(0084)

Output Current at

Previous Fault

Output Current

Displays the output current at the previous fault.

Note:

The unit is expressed in 1 A for models 4A0930

and 4A1200.

No signal output

available

<1>

<2>

U2-07

(0086)

Output Voltage at

Previous Fault

Output Voltage

Displays the output voltage at the previous fault.

No signal output

available

0.1 Vac

U2-08

(0087)

DC Bus Voltage at

Previous Fault

DC Bus Voltage

Displays the DC bus voltage at the previous fault.

No signal output

available

1 Vdc

U2-09

(0088)

Output Power at

Previous Fault

Output kWatts

Displays the output power at the previous fault.

No signal output

available

0.1 kW

U2-10

(0089)

Torque Reference at

Previous Fault

Torque Reference

OLV

OLV

OLV

OLV

Displays the torque reference at the previous fault.

No signal output

available

0.1%

U2-11

(008A)

Input Terminal Status at

Previous Fault

Input Term Sts

Displays the input terminal status at the previous fault.

Displayed as in U1-10.

No signal output

available

U2-12

(008B)

Output Terminal Status

at Previous Fault

Output Term Sts

Displays the output status at the previous fault. Displays the

same status displayed in U1-11.

No signal output

available

U2-13

(008C)

Drive Operation Status

at Previous Fault

Inverter Status

Displays the operation status of the drive at the previous fault.

Displays the same status displayed in U1-12.

No signal output

available

U2-14

(008D)

Cumulative Operation

Time at Previous Fault Elapsed time

Displays the cumulative operation time at the previous fault.

No signal output

available

1 h

U2-15

(07E0)

Soft Starter Speed

Reference at Previous

Fault

SFS Output

Displays the speed reference for the soft starter at the previous

fault.

No signal output

available

0.01 Hz

U2-16

(07E1)

Motor q-Axis Current at

Previous Fault

Motor Iq Current

Displays the q-axis current for the motor at the previous fault. No signal output

available

0.10%

U2-17

(07E2)

Motor d-Axis Current at

Previous Fault

Motor Id Current

OLV

OLV

OLV

OLV

Displays the d-axis current for the motor at the previous fault.

No signal output

available

0.10%

U2-20

(008E)

Heatsink Temperature

at Previous Fault

Actual Fin Temp

Displays the temperature of the heatsink when the most recent

fault occurred.

No signal output

available

1 °C

U2-27

(07FA)

Motor Temperature at

Previous Fault (NTC)

Moter temp (NTC)

Displays the temperature of the motor when the most recent

fault occurred. Displayed as in U4-32.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

1 °C

U2-28

(07FC) Malfunctioned Module Fault Axis

Display the module where the previous fault occurred at a

decimal number.

Note:

This monitor is only displayed in models 4A0930

and 4A1200.

No signal output

available

U2-30

(3008)

Date Year at Previous

Fault

Date Year YYYY

Displays the year when the most recent fault occurred.

No signal output

available

U2-31

(3009)

Date Month and Day at

Previous Fault

Date Mo Day MMDD Displays the date and day when the most recent fault occurred. No signal output

available

U2-32

(300A)

Time Hours and

Minutes at Previous

Fault

Time Hr Min HHMM

Displays the time when the most recent fault occurred.

No signal output

available

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

B.15 U: Monitors

404

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising