P2-01: sleep level type, P2-02: sleep level – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 228

Advertising
background image

H igh F eedba ck D etection

Inverse PID (b5-09 = 1)

Ou tpu t

F requen cy

Au to R un

C omm an d

PID

F eedba ck

D uring

Pre-C ha rge

P1-11 – H igh F B Le vel

P1-14

P1-12

H gh LVL F lt T m

P1-12

H gh LVL F lt T m

P1-12

H gh LVL F lt T m

“H igh F eedba ck

H igh F B Sen sed ”

Alarm & D igital

Ou tpu t (H 2-0x = 96)

“HF B – H igh

F eedba ck” F au lt

H igh F eedba ck Se l = F au lt (P1-13 = 0)

Figure 4.44 High Feedback Detection Inverse PID

Setting 1: Alarm

When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”

(H2-0o= 96) closes and the drive displays the “High Feedback – High FB Sensed” alarm.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high

feedback detection are no longer true, the digital output will open and the alarm will clear.

Setting 2: Digital out only

When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to “High Feedback”

(H2-0o= 96) closes.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high

feedback detection are no longer true, the digital output will open.

n

P2-01: Sleep Level Type

Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-

dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents

a low-activity condition for the system.

Note:

Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.

No.

Parameter Name

Setting Range

Default

P2-01

Sleep Level Type

0 to 4

0

Setting 0: Output frequency
Setting 1: Output current
Setting 2: Feedback
Setting 3: Output speed (RPM)
Setting 4: Flow meter (requires flow meter)

n

P2-02: Sleep Level

Sets the level at which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls below

the P2-02 setting for the time set in P2-03.

No.

Parameter Name

Setting Range

Default

P2-02

Sleep Level

0.0 to 6000.0

0.0 Hz

4.6 Basic iQpump Setup and Application Preset Parameters

228

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide