4.2 Powering Up the Drive

Review the following table before applying power.

Item to Check

Description

Power supply voltage

200 V class: Three-phase/Single-phase 200 to 240 Vac 50/60 Hz

400 V class: Three-phase/Single-phase 380 to 480 Vac 50/60 Hz

600 V class: Three-phase/Single-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).

<1>

Check for proper grounding of drive and motor.

Drive output terminals and

motor terminals

Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load and connected

machinery

Decouple the motor from the load.

<1> Confirm the following when connecting models 4A0930 and 4A1200: Remove the jumpers on R1/L11, S1/L21, and T1/L31 when using 12-phase

rectification.

Refer to 12-Phase Rectification on page 123

for details. When operating without 12-phase rectification, properly wire terminals R1/

L11, S1/L21, and T1/L31 in addition to terminals R/L1, S/L2, and T/L3.

u

Setting the Real Time Clock

When the drive is powered up for the first time, the time and date must be set. The HOA keypad will display the time and date

setup screen for 30 seconds. If a button is not pressed during this time, the display will clear and a “Clock Not Set” alarm will

flash. Pressing the F2 (Data) key will display the setting screen again.

n

Feedback Loss Wire Break Alarm

If there is no sensor wired to the drive, a “Feedback Loss – Wire Break” alarm will flash on the display after the 30-second

time and date screen has elapsed (not the “Clock Not Set” alarm). Providing the proper feedback device signal will clear the

Feedback Loss alarm. The “Clock Not Set” alarm will then flash.
The drive requires a feedback device (e.g., pressure transducer, flow meter, etc.) to perform automatic system regulation. Any

analog 0~10 V or 4-20 mA feedback device can be used in combination with the drive.

Note:

The factory default setting for the drive is 4~20 mA feedback device connected to analog input A2.

n

Real Time Clock Setting Display

Note:

Setting the Real-Time Clock will clear a “TIM” alarm.

20

1

0/01/01 00:00

Second per month

+ 0 sec

YYYY/MM/DD HH:MM

FWD

A

B

A – Real Time Clock Setting Display

Set in 24-Hour Clock Time

B – Gain/Loss Adjustment Display

Figure 4.1 Real Time Clock Adjustment Display

Display

Description

YYYY

Set the year with the last two digits.

MM

Set the month with two digits.

DD

Set the day with two digits.

4.2 Powering Up the Drive

158

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide