Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 394
Advertising
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Q5-19
(0F32)
Suction Pressure
Analog Input Wire-
Break Detection
SP Wire Break
0: No Display
1: Alarm Only
2: Fault
Sets the behavior when the analog input selected for suction
pressure feedback is programmed to receive a 4 to 20 mA signal
and the signal is lost.
0: Disabled
1: Alarm only
2: Fault (no retry, coast to stop)
Default: 2
Range: 0 to 2
–
<1> Units are determined by Q5-01, Suction Pressure Select, setting.
<2> Units are determined by Q5-18, Suction Pressure Detection Time Unit, setting.