B.6 F: Options

u

F4: Analog Monitor Card (AO-A3)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F4-01

(0391)

Terminal V1 Monitor

Selection

AO Ch1 Select

Sets the monitor signal for output from terminal V1. Set this

parameter to the last three digits of the desired Uo-oo

monitor. Some U parameters are available only in certain control

modes.

Default: 102

Range: 000 to

999

F4-02

(0392)

Terminal V1 Monitor

Gain

AO Ch1 Gain

Sets the gain for voltage output via terminal V1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

F4-03

(0393)

Terminal V2 Monitor

Selection

AO Ch2 Select

Sets the monitor signal for output from terminal V2. Set this

parameter to the last three digits of the desired Uo-oo

monitor. Some U parameters are available only in certain control

modes.

Default: 103

Range: 000 to

999

F4-04

(0394)

Terminal V2 Monitor

Gain

AO Ch2 Gain

Sets the gain for voltage output via terminal V2.

Default: 50.0%

Min.: -999.9

Max.: 999.9

F4-05

(0395)

Terminal V1 Monitor

Bias

AO Ch1 Bias

Sets the amount of bias added to the voltage output via terminal

V1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

F4-06

(0396)

Terminal V2 Monitor

Bias

AO Ch2 Bias

Sets the amount of bias added to the voltage output via terminal

V2.

Default: 0.0%

Min.: -999.9

Max.: 999.9

F4-07

(0397)

Terminal V1 Signal

Level

AO Opt Level Ch1

0: 0-10 VDC

1: -10 +10 VDC

0: 0 to 10 V

1: -10 to 10 V

Default: 0

Range: 0, 1

F4-08

(0398)

Terminal V2 Signal

Level

AO Opt Level Ch2

0: 0-10 VDC

1: -10 +10 VDC

0: 0 to 10 V

1: -10 to 10 V

Default: 0

Range: 0, 1

u

F5: Digital Output Card (DO-A3)

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

F5-01

(399)

Terminal P1-PC Output

Selection

DO Ch1 Select

Sets the function for contact output terminals M1-M2, M3-M4,

and photocoupler output terminals P1 through P6.

Refer to H2: Multi-Function Digital Outputs on page 352

for

setting selections.

Default: 0

Range: 0 to 192

F5-02

(39A)

Terminal P2-PC Output

Selection

DO Ch2 Select

Default: 1

Range: 0 to 192

F5-03

(39B)

Terminal P3-PC Output

Selection

DO Ch3 Select

Default: 2

Range: 0 to 192

F5-04

(39C)

Terminal P4-PC Output

Selection

DO Ch4 Select

Default: 4

Range: 0 to 192

F5-05

(39D)

Terminal P5-PC Output

Selection

DO Ch5 Select

Default: 6

Range: 0 to 192

F5-06

(39E)

Terminal P6-PC Output

Selection

DO Ch6 Select

Default: 37

Range: 0 to 192

F5-07

(39F)

Terminal M1-M2

Output Selection

DO Ch7 Select

Default: F

Range: 0 to 192

F5-08

(3A0)

Terminal M3-M4

Output Selection

DO Ch8 Select

Default: F

Range: 0 to 192

F5-09

(3A1)

DO-A3 Output Mode

Selection

DO Function Sel

0: 8ch Individual

1: Binary Output

2: 8ch Selected

0: Output terminals are each assigned separate output functions.

1: Binary code output.

2: Use output terminal functions selected by parameters F5-01

through F5-08.

Default: 0

Range: 0 to 2

B.6 F: Options

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

343

B

Parameter List