2 powering up the drive – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 160

Advertising
background image

Table 4.2 Manual Clock Adjustment Procedure by Setting o4-17 to 1

Procedure

Display

1

The “Clock Not Set” display will appear if the Real-Time Clock data is not entered within 30

seconds of power-up on a new drive.

- MODE -

DATA

DRV Rdy

ALM

FWD

ALM

Clock Not Set

Press F2 to Set

2

Use the up and down arrow keys to scroll through display menu until the screen shows

“Programming”.

- MODE -

DATA

HELP

PRG

ALM

Programming

FWD

3

Press the ENTER key to enter select the parameter setting mode.

- PRMSET - PRG

ALM

Initialization

A1-00 = 0

Select Language

FWD

ALM

4

Use the up and down arrow keys to scroll through display menu until parameter o4-17 appears.

- PRMSET - PRG

ALM

Maintenance

o4-17 = 0

Set time

FWD

ALM

5

Press the ENTER key until “0” flashes.

- PRMSET - PRG

ALM

Set time

o4-17=

0

*0*

- -

“0”

FWD

ALM

6

Press the up arrow key so that the display changes to “1”.

- PRMSET - PRG

ALM

Set time

o4-17=

1

*0*

Set

“0”

FWD

ALM

7

Press the ENTER key and the time setting screen will appear. Use the right arrow key to select

the desired digit, then set the correct date and time using the up and down arrow keys.

ALM

20

1

0/01/01 00:00

Second per month

+ 0 sec

YYYY/MM/DD HH:MM

ALM

8

After entering the correct time, press the ENTER key to save the changes.

The display will return to the display shown in step 5 and the alarm LED will be OFF.

ALM

Entry accepted

n

o4-17: Real-Time Clock Setting (Resetting RTC Back to Factory Default)

No.

(Addr.

Hex)

Name

Description

Values

o4-17

(3100)

Set/Reset Real-time Clock

Sets the current date and time for the Real-Time Clock.

0: — — No Setting

1: Real-Time Clock Set

2: Real-Time Clock Reset

Default: 0

Range: 0 to 2

4.2 Powering Up the Drive

160

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide