b3-08

(0198)

Current Control Gain

during Speed Search

(Speed Estimation

Type)

Srch ACR P Gain

Sets the proportional gain for the current controller during Speed

Search.

Default: 0.8

Min.: 0.00

Max.: 6.00

b3-10

(019A)

Speed Search Detection

Compensation Gain

Srch Detect Comp

Sets the gain which is applied to the speed detected by Speed

Estimation Speed Search before the motor is reaccelerated.

Increase this setting if ov occurs when performing Speed Search

after a relatively long period of baseblock.

Default: 1.05

Min.: 1.00

Max.: 1.20

b3-14

(019E)

Bi-Directional Speed

Search Selection

Bidir Search Sel

0: Disabled

1: Enabled

0: Disabled (uses the direction of the frequency reference)

1: Enabled (drive detects which way the motor is rotating)

Default: 1

Range: 0, 1

b3-17

(01F0)

Speed Search Restart

Current Level

SrchRestart Lvl

Sets the Speed Search restart current level as a percentage of the

drive rated current.

Default: 150%

Min.: 0

Max.: 200

b3-18

(01F1)

Speed Search Restart

Detection Time

SrchRestart Time

Sets the time to detect Speed Search restart.

Default: 0.10 s

Min.: 0.00

Max.: 1.00

b3-19

(01F2)

Number of Speed

Search Restarts

Num of SrchRestr

Sets the number of times the drive can attempt to restart when

performing Speed Search.

Default: 3

Min.: 0

Max.: 10

b3-24

(01C0)

Speed Search Method

Selection

SpdSrch Method

0: CurrentDetection

1: Speed Estimation

0: Current Detection

1: Speed Estimation

Default: 0

Range: 0, 1

b3-25

(01C8) Speed Search Wait Time SpdSrch WaitTime

Sets the time the drive must wait between each Speed Search

restart attempt.

Default: 0.5 s

Min.: 0.0

Max.: 30.0

b3-26

(01C7)

Direction Determining

Level

Spd Search Meth

Sets the level that determines the direction of motor rotation.

Note:

This parameter is only available in models

4A0930 and 4A1200.

Default:

<1>

Min.: 40

Max.: 60000

b3-27

(01C9)

Start Speed Search

Select

Start srch sel

0: Start from 0

1: Start Fref>Fmin

Selects a condition to activate Speed Search Selection at Start

(b3-01) or External Speed Search Command 1 or 2 from the

multi-function input.

0: Triggered when a Run command is issued (normal).

1: Triggered when an external baseblock is released.

Default: 0

Range: 0, 1

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

b4: Timer Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b4-01

(01A3)

Timer Function On-

Delay Time

Delay-ON Timer

Sets the on-delay and off-delay times for a digital timer output

(H2-oo=12).

The output is triggered by a digital input programmed to

H1-oo=18).

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

b4-02

(01A4)

Timer Function Off-

Delay Time

Delay-OFF Timer

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

u

b5: PID Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b5-01

(01A5) PID Function Setting

PID Mode

0: Disabled

1: Enabled D=Fdbk

0: Disabled

1: Enabled (PID output becomes output frequency reference,

deviation D controlled)

Default: 1

Range: 0, 1

214

b5-02

(01A6) Proportional Gain

Setting (P)

PID Gain

Sets the proportional gain of the PID controller.

The function of b5-02 is disabled when P1-24 > 0

Default: 2.00

Min.: 0.00

Max.: 25.00

B.2 b: Application