L7: Torque Limit

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L7-01

(04A7) Forward Torque Limit Torq Limit Fwd

OLV

OLV

OLV

OLV

Sets the torque limit value as a percentage of the motor rated

torque. Four individual quadrants can be set.

L7-01

L7-03

L7-02

L7-04

Output Torque

Positive Torque

REV

Negative Torque

FWD

Motor
r/min

Regeneration

Regeneration

Default: 200%

Min.: 0

Max.: 300

L7-02

(04A8) Reverse Torque Limit Torq Limit Rev

Default: 200%

Min.: 0

Max.: 300

L7-03

(04A9)

Forward Regenerative

Torque Limit

Torq Lmt Fwd Rgn

Default: 200%

Min.: 0

Max.: 300

L7-04

(04AA)

Reverse Regenerative

Torque Limit

Torq Lmt Rev Rgn

Default: 200%

Min.: 0

Max.: 300

L7-06

(04AC)

Torque Limit Integral

Time Constant

Trq Lim I Time

OLV

OLV

OLV

OLV

Sets the integral time constant for the torque limit.

Default: 200 ms

Min: 5

Max: 10000

L7-07

(04C9)

Torque Limit Control

Method Selection

during Accel/Decel

Trq Lim d AccDec

0: P-ctrl @ Acc/Dec

1: I-ctrl @ Acc/Dec

OLV

OLV

OLV

OLV

0: Proportional control (changes to integral control at constant

speed). Use this setting when acceleration to the desired speed

should take precedence over the torque limit.

1: Integral control. Set L7-07 to 1 if the torque limit should take

precedence.

Default: 0

Range: 0, 1

u

L8: Drive Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L8-01

(04AD)

Internal Dynamic

Braking Resistor

Protection Selection

(ERF type)

DB Resistor Prot

0: Not Provided

1: Provided

0: Resistor overheat protection disabled

1: Resistor overheat protection enabled

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 0

Range: 0, 1

L8-02

(04AE) Overheat Alarm Level OH Pre-Alarm Lvl

An overheat alarm occurs when heatsink temperature exceeds

the L8-02 level.

Default:

<1>

Min.: 50 °C

Max.: 150 °C

L8-03

(04AF)

Overheat Pre-Alarm

Operation Selection

OH Pre-Alarm Sel

0: Ramp to stop

1: Coast to stop

2: Fast-Stop

3: Alarm only

4: Run@L8-19 Rate

0: Ramp to stop. A fault is triggered.

1: Coast to stop. A fault is triggered.

2: Fast Stop. Decelerate to stop using the deceleration time in

C1-09. A fault is triggered.

3: Continue operation. An alarm is triggered.

4: Continue operation at reduced speed as set in L8-19.

Default: 3

Range: 0 to 4

L8-05

(04B1)

Input Phase Loss

Protection Selection

Inp Ph Loss Det

0: Disabled

1: Enabled

Selects the detection of input current phase loss, power supply

voltage imbalance, or main circuit electrolytic capacitor

deterioration.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

L8-07

(04B3)

Output Phase Loss

Protection Selection

Outp Ph Loss Det

0: Disabled

1: 1PH Loss Det

2: 2/3PH Loss Det

0: Disabled

1: Enabled (triggered by a single phase loss)

2: Enabled (triggered when two phases are lost)

Default: 1

Range: 0 to 2

L8-09

(04B5)

Output Ground Fault

Detection Selection

Grnd Flt Det Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

L8-10

(04B6)

Heatsink Cooling Fan

Operation Selection

Fan On/Off Sel

0: Dur Run (OffDly)

1: Always On

0: During run only. Fan operates only during run for L8-11

seconds after stop.

1: Fan always on. Cooling fan operates whenever the drive is

powered up.

Default: 0

Range: 0, 1

L8-11

(04B7)

Heatsink Cooling Fan

Off Delay Time

Fan Delay Time

Sets a delay time to shut off the cooling fan after the Run

command is removed when L8-10 = 0.

Default: 300 s

Min.: 0

Max.: 300

B.8 L: Protection Function