Terminal configuration, Wire size and torque specifications, 7 control circuit wiring – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 145

Advertising
background image

u

Terminal Configuration

The control circuit terminals are arranged as shown in

Figure 3.26

.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

Figure 3.26 Control Circuit Terminal Arrangement

n

Wire Size and Torque Specifications

Select appropriate wire type and gauges from

Table 3.10

. For simpler and more reliable wiring, use crimp ferrules on the wire

ends. Refer to

Table 3.11

for ferrule terminal types and sizes.

Table 3.10 Wire Gauges

Terminal

Screw

Size

Tightening

Torque

N

m

(lb. in)

Bare Wire Terminal

Ferrule-Type Terminal

Wire Type

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

S1-S8, SC, SN, SP

M3

0.5 to 0.6

(4.4 to 5.3)

Stranded wire:

0.2 to 1.0

(24 to 16)

Solid wire:

0.2 to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

Shielded wire,

etc.

RP, V+, A1, A2, A3,

AC, 24 V
MA, MB, MC, MD, ME,

MF
M1-M4
FM, AM, AC
R+, R-, S+, S-, IG

3.7 Control Circuit Wiring

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

145

3

Electrical Installation

Advertising