Q5-11: Low Suction Pressure Behavior Select

Selects the drive response to a Low Suction Pressure condition. When the suction pressure feedback falls below the Q5-09

setting for the time set in Q5-10, the drive will respond based on the setting in Q5-11. By setting Q5-11 to 3 (Restart Q5-15),

the drive will attempt to reset itself for the number of times set in L5-01 waiting for the Q5-15 reset time before each reset

attempt. The drive will fault if the L5-01 attempts are exceeded.

No.

Parameter Name

Setting Range

Default

Q5-11

Low Suction Pressure Behavior Select

0 to 3

1

Setting 0: No display (digital output only)
Setting 1: Alarm only
Setting 2: Fault
Setting 3: Auto-restart (time set in Q5-15)

n

Q5-16: Suction Control Proportional Gain

Sets the proportional gain of the Suction Pressure controller. Increasing this value will make the system more responsive but

can lead to instability. Q5-16 is used in place of b5-02 for suction pressure control.

No.

Parameter Name

Setting Range

Default

Q5-16

Suction Control Proportional Gain

0.00 to 25.00

2.00

n

Q5-17: Suction Control Integral Time

Sets the integral time of the Suction Pressure controller. Decreasing this value will make the system more responsive but can

lead to overshoot. Q5-17 is used in place of b5-03 for suction pressure control.

No.

Parameter Name

Setting Range

Default

Q5-17

Suction Control Integral Time

0.0 to 360.0 s

5.0 s

4.6 Basic iQpump Setup and Application Preset Parameters

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

235