Flange type heat loss data – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 58
n
Flange Type Heat Loss Data
Table 2.13 Models 2A0018 and 2A0021, 4A0007 to 4A0011, and 5A0006 and 5A0009
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
2A0018
200
67.4
100.7
168.1
60.0
77.0
137.0
3.7 (8.1)
2A0021
83.3
138.4
221.7
67.4
100.7
168.1
3.7 (8.1)
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
4A0007
400
59.0
62.1
121.1
53.0
47.7
100.7
3.6 (7.9)
4A0009
60.4
65.8
126.2
55.3
53.1
108.4
3.7 (8.1)
4A0011
73.0
88.7
161.7
61.0
68.5
129.5
3.7 (8.1)
Drive Model
Voltage
Class
Heat Loss (W)
Wt. kg (lb)
ND (Fc = 2 kHz)
HD (Fc = 8 kHz)
Internal
External
Total
Internal
External
Total
5A0006
600
43.7
28.1
71.8
27.0
53.0
80.0
3.7 (8.1)
5A0009
68.9
43.4
112.3
36.4
78.7
115.1
3.7 (8.1)
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss
58
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide