Flange type heat loss data – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 58

Advertising
background image

n

Flange Type Heat Loss Data

Table 2.13 Models 2A0018 and 2A0021, 4A0007 to 4A0011, and 5A0006 and 5A0009

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

2A0018

200

67.4

100.7

168.1

60.0

77.0

137.0

3.7 (8.1)

2A0021

83.3

138.4

221.7

67.4

100.7

168.1

3.7 (8.1)

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

4A0007

400

59.0

62.1

121.1

53.0

47.7

100.7

3.6 (7.9)

4A0009

60.4

65.8

126.2

55.3

53.1

108.4

3.7 (8.1)

4A0011

73.0

88.7

161.7

61.0

68.5

129.5

3.7 (8.1)

Drive Model

Voltage

Class

Heat Loss (W)

Wt. kg (lb)

ND (Fc = 2 kHz)

HD (Fc = 8 kHz)

Internal

External

Total

Internal

External

Total

5A0006

600

43.7

28.1

71.8

27.0

53.0

80.0

3.7 (8.1)

5A0009

68.9

43.4

112.3

36.4

78.7

115.1

3.7 (8.1)

2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss

58