P1-10

(0C09)

Low Feedback

Selection

Low FB Sel

0: Fault

1: Alarm

2: Digital Output

Selects drive response during the “Low Feedback” condition.

0: Fault

1: Alarm

2: Digital out only

Default: 0

Range: 0 to 2

225

P1-11

(0C0A) High Feedback Level

High FB Level

Sets the upper detection level for the PID feedback.

Default: 155.0
PSI

<2>

Min.: 0.0

Max.: 6000.0

227

P1-12

(0C0B) High Feedback Level

Fault Delay Time

High Lvl FLT Time

Sets the amount of delay time from when the high feedback is

detected until the drive faults on a “HFB High Feedback” fault.

Note:

This parameter is effective only when P1-13 is set

to 0 (Fault (and digital out)).

Default: 5 s

Min.: 0

Max.: 3600

227

P1-13

(0C0C)

High Feedback

Selection

High FB Sel

0: Fault

1: Alarm

2: Digital Output

Selects drive response during the “High Feedback” condition.

0: Fault

1: Alarm

2: Digital out only

Default: 0

Range: 0 to 2

227

P1-14

(0C0D) Hysteresis Level

Hysteresis Level

Sets the hysteresis level used for low and high level feedback

detection.

Default: 0.0 PSI

<2>

Min.: 0.0

Max.: 100.0

P1-15

(0C0E) Maximum Setpoint

Difference

Max Set Pnt Diff

Sets the level that the difference between the setpoint and the

feedback must exceed for the time set in P1-16 to trigger the

drive response set in P1-17.

If P1-17 is set to 1 (Fault and digital out), the will coast to stop.

This function is active when the drive is running during AUTO

Mode. When P1-01 is set to 3 (MEMOBUS network), the

function is active on the lead drive and will stop all drives

running on the network when The NMS fault occurs.

Setting this parameter to 0.0 disables the function.

Default: 0.0 PSI

<2>

Min.: 0.0

Max.: 6000.0

P1-16

(0C0F) Not Maintaining

Setpoint Time

Not Maint SP Tm

Sets the delay time before a “Setpoint Not Met” condition

occurs. The pump protection criteria set in P1-15 must be met

before the timer will start.

Setting P1-15 to 0.0 disables this function.

Default: 60 s

Min.: 0

Max.: 3600

P1-17

(0C10)

Not Maintaining

Setpoint Selection

Not Maint SP Sel

0: Fault

1: Alarm

2: Digital Output

Selects the drive response method during the “Not Maintaining

Setpoint” condition.

0: Fault

1: Alarm

2: Digital out only

Default: 0

Range: 0 to 2

P1-18

(0C11)

Prime Loss Detection

Method

Prime Loss Mthd

0: Current (A)

1: Power (kW)

2: Torque (%)

Determines the quantity used to determine loss of prime.

0: Current (A)

1: Power (kW)

2: Torque (%)

Default: 0

Range: 0 to 2

P1-19

(0C12) Prime Loss Level

Prime Loss Level

Detects loss of prime in the pump when in Auto or Sleep Boost

Mode.

When the measured quantity determined by P1-18 drops below

this level for the time set in P1-20 and the output frequency is

above the level set in P1–21, a “Loss of Prime” condition occurs.

The drive responds to the “Loss of Prime” condition depending

on the setting of P1-22, Loss of Prime Selection.

Default: 0.0 A

<4>

Min.: 0.0

Max.: 1000.0

P1-20

(0C13) Loss of Prime Time

Prime Loss Time

Sets the delay time before a “Loss of Prime” condition occurs.

The pump protection criteria set in P1-18 and P1-19 must be met

before the timer will start.

Default: 20 s

Min.: 0

Max.: 600

P1-21

(0C14)

Loss of Prime

Frequency

Prime Loss Freq

Sets the frequency level above which the “Loss of Prime”

detection is enabled when set to a value other than 0.

When set to 0 (default), the frequency level is determined by the

smaller value between (Fmax - 1 Hz) and (d2-01 - 1 Hz).

Default: 0.0 Hz

Min.: 0.0

Max.: [E1-04]

P1-22

(0C15) Loss of Prime Selection

Prime Loss Sel

0: Fault

1: Alarm

2: Digital Output

Sets the drive response method during the “Loss of Prime”

condition.

0: Fault

1: Alarm

2: Digital out only

Default: 0

Range: 0 to 2

P1-23

(0C16)

Loss of Prime

Maximum Restart Time

after Fault

LOP Max Rstrt T

Sets the time in minutes that the drive will wait before

attempting another restart when the restart fails or is not

attempted due to a continuing fault condition.

Default: 0.2 min

Min.: 0.2

Max.: 6000.0