E2-01: motor rated current, E2-04: number of motor poles – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 216

Advertising
background image

Table 4.19 Accel/Decel Time Selection by Digital Input

Accel/Decel Time Sel. 1

H1-oo = 7

Accel/Decel Time Sel. 2

H1-oo = 1A

Active Times

Acceleration

Deceleration

0

0

C1-01

C1-02

1

0

C1-03

C1-04

Figure 4.36

shows an operation example for changing accel/decel. times. The example below requires that the stopping method

be set for “Ramp to stop” (b1-03 = 0).

Output

frequency

Accel Time 1

(C1-01)

Decel Time 1

(C1-02)

Accel Time 2

(C1-03)

Decel Time 2

(C1-04)

Decel Time 1

(C1-02)

Time

FWD (REV)

Run command

ON

OFF

ON

ON

Accel/Decel Time Selection 1

(Terminals S1 to S8, H1-oo = “7”)

OFF

Figure 4.36 Timing Diagram of Accel/Decel Time Change

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

<1>

Determined by

C6-01 and o2-04

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

Note:

An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to

prevent this error.

n

E2-04: Number of Motor Poles

Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically

be saved to E2-04.

No.

Parameter Name

Setting Range

Default

E2-04

Number of Motor Poles

2 to 48

2

n

H1-01 to H1-08: Functions for Terminals S1 to S8

These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in

Table

4.20

.

No.

Parameter Name

Setting

Range

Default

H1-01

Multi-Function Digital Input Terminal S1 Function Selection

1 to 9F

40 (F)

<1>

: Forward Run Command (2-Wire sequence)

H1-02

Multi-Function Digital Input Terminal S2 Function Selection

1 to 9F

F: Through Mode

H1-03

Multi-Function Digital Input Terminal S3 Function Selection

0 to 9F

26: External Pump Fault

H1-04

Multi-Function Digital Input Terminal S4 Function Selection

0 to 9F

14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

0 to 9F

8D (0)

<1>

: Multi Setpoint 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

0 to 9F

80 (3)

<1>

: HAND Mode

4.6 Basic iQpump Setup and Application Preset Parameters

216

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide