Temperature derating, Parameter settings – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 322

Advertising
background image

Drive Model

Output Capacity

Single Phase Input Load

Motor Power (HP)

Motor FLA

Power (kVA)

Current (A)

4A0362

125

156

142

308

4A0414

150

180

168

365

4A0515

150

180

171

371

4A0675

200

240

225

489

Table A.20 Sizing Method B, 600 V Single-Phase Input (575 V to 600 V), 575 V Three-Phase Motor

Drive Model

Output Capacity

Single Phase Input Load

Motor Power (HP)

Motor FLA

Power (kVA)

Current (A)

5A0003

1

1.7

1.78

3.10

5A0004

2

2.7

2.93

5.10

5A0006

3

3.9

4.37

7.60

5A0009

5

6.1

6.90

12.0

5A0011

3

3.9

4.95

8.60

5A0017

7.5

9

11.4

19.8

5A0022

7.5

9

11.4

19.8

5A0027

10

11

16.1

28.0

5A0032

10

11

16.1

28.0

5A0041

20

22

24.0

41.8

5A0052

20

22

24.0

41.8

5A0062

30

32

36.8

64.0

5A0077

40

41

46.0

80.0

5A0099

40

41

47.2

82.0

5A0125

60

62

68.4

119

5A0145

60

62

68.4

119

5A0192

100

99

113

196

5A0242

100

99

113

196

u

Temperature Derating

To ensure the maximum performance life, the drive output current must be derated as shown in

Figure A.1

when the drive is

installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable

drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.

n

Parameter Settings

No.

Name

Description

Range

Def.

L8-12

Ambient

Temperature Setting

Adjust the drive overload (oL2) protection level when the drive is installed

in an environment that exceeds its ambient temperature rating.

-10 to +50

+40 °C

L8-35

Installation Method

Selection

0: IP00/Open-Chassis Enclosure

1: Side-by-Side Mounting

2: IP20/NEMA Type 1 Enclosure

3: Finless Drive or External Heatsink Installation

0 to 3

<1>

<1> Default setting is determined by drive model.

Setting 0: (Models 2A0250 to 2A0415 and 4A0208 to 4A1200)
Setting 2: (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242).

Setting 0: IP00/Open-Chassis Enclosure

Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.

Setting 1: Side-by-Side Mounting

Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and

+50 °C requires output current derating.

Setting 2: IP20/NEMA Type 1 Enclosure

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

A.4 Drive Derating Data

322

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

Advertising