HOA Keypad Display

Fault Name

oFb02

Option Card Fault at Option Port CN5-B
Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is already

installed in option port CN5-A

Only one of each option card type can only be installed simultaneously. Make sure only one type of option

card is connected.

An input option card is already installed in

option port CN5-A

Install a communication option. More than one of the same type of card cannot be installed simultaneously.

HOA Keypad Display

Fault Name

oFb03 to oFb11

Option card error occurred at Option Port CN5-B

oFb12 to oFb17

Cause

Possible Solution

Option card or hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

oFC00

Option Card Connection Error at Option Port CN5-C
Option compatibility error

Cause

Possible Solution

The option card installed into port CN5-C

is incompatible with the drive

Confirm that the drive supports the option card to be installed. Contact Yaskawa for assistance.

A communication option card has been

installed in option port CN5-C

Communication option cards are only supported by option port CN5-A. It is not possible to install more than

one communication option.

HOA Keypad Display

Fault Name

oFC01

Option Card Fault at Option Port CN5-C
Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-C

is faulty.

• Turn the power off and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in a different option port. If the option card works properly in a different option port,

CN5-C is damaged, and the drive requires replacement. If the error persists (oFA01 or oFb01 occur),

replace the option card.

HOA Keypad Display

Fault Name

oFC02

Option Card Fault at Option Port CN5-C
Same type of option card is currently connected

Cause

Possible Solution

An option card of the same type is already

installed in option port CN5-A or CN5-B.

Only one of each option card type can only be installed simultaneously. Make sure only one type of option

card is connected.

An input option card is already installed in

option port CN5-A or CN5-B.

Install a communication option, a digital input option, or an analog input option. More than one of the same

type of card cannot be installed simultaneously.

HOA Keypad Display

Fault Name

oFC03 to oFC11

Option Card Error Occurred at Option Port CN5-C

oFC12 to oFC17

Cause

Possible Solution

Option card or hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

oFC50 to oFC55

Option Card Error Occurred at Option Port CN5-C

Cause

Possible Solution

Option card or hardware is damaged

Refer to the option manual for details.

5.2 Fault Detection

250

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide