Drive fails to operate properly due to noise

interference

• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference and check the control circuit lines, main circuit lines,

and ground wiring.

Overexcitation gain is set too high

• Check if the fault occurs simultaneously with overexcitation function operation.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).

Run command was applied while motor

was coasting

• Set b3-01 to 1 to enable Speed Search at Start.
• Program the Speed Search command input through one of the multi-function contact input terminals

(H1-oo = 61 or 62).

The rated output current of the drive is too

small

Use a larger drive.

HOA Keypad Display

Fault Name

oFA00

Option Card Connection Error at Option Port CN5-A
Option compatibility error

Cause

Possible Solution

The option card installed into port CN5-A

is incompatible with the drive

Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.

HOA Keypad Display

Fault Name

oFA01

Option Card Fault at Option Port CN5-A
Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-A

is faulty

• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the option

card works properly in a different option port, CN5-A is damaged, and the drive requires replacement. If

the error persists (oFb01 or oFC01 occur), replace the option card.

HOA Keypad Display

Fault Name

oFA03 to oFA06

Option Card Error Occurred at Option Port CN5-A

oFA10, oFA11

oFA12 to oFA17

Option Card Connection Error (CN5-A)

oFA30 to oFA43

Communication Option Card Connection Error (CN5-A)

Cause

Possible Solution

Option card or hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

oFb00

Option Card Fault at Option Port CN5-B
Option compatibility error

Cause

Possible Solution

The option card installed into port CN5-B

is incompatible with the drive

Make sure the drive supports the option card to be installed. Contact Yaskawa for assistance.

A communication option card has been

installed in option port CN5-B

Communication option cards are only supported by option port CN5-A. It is not possible to install more than

one communication option.

HOA Keypad Display

Fault Name

oFb01

Option Card Fault at Option Port CN5-B
Option not properly connected

Cause

Possible Solution

The option card connection to port CN5-B

is faulty

• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in a different option port. If the option card works properly in a different option port,

CN5-B is damaged, and the drive requires replacement. If the error persists (oFA01 or oFC01 occur),

replace the option card.

5.2 Fault Detection

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

249

5

Troubleshooting