Drive Model

Normal Duty

Nominal

Output Power

HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay Fuse

Rating Amps

<2>

Non-time Delay

Fuse Rating

Amps

<3>

Bussmann Semi-

conductor Fuse

Rating (Fuse

Ampere)

<4>

5A0125

125

129

225

225

350

FWP-350A (350)

5A0145

150

158

300

275

450

FWP-350A (350)

5A0192

200

228

400

350

600

FWP-600A (600)

5A0242

250

263

500

450

700

FWP-600A (600)

<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussman FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class models

and FWP fuses for 600 V models.

<5> Class L fuse is also approved for this rating.

Wiring Fuses for Models 4A0930 and 4A1200

NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices

to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage

current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from

Table 3.2

.

Table D.6 Input Fuses for Models 4A0930 and 4A1200

Voltage

Class

Model

Selection

Input Fuse (Example)

Input Voltage

Current

Pre-arc

I

2

t (A

2

s)

Model

Manufacturer

Rating

Pre-arc

I

2

t (A

2

s)

Three-

Phase

400 V

Class

4A0930

480 V

1500 A

140000 to

3100000

CS5F-1200

Fuji Electric

AC500 V, 1200 A

276000

FWH-1200A

Bussman

AC500 V, 1200 A

4A1200

480 V

1500 A

320000 to

3100000

CS5F-1500

Fuji Electric

AC500 V, 1500 A

351000

FWH-1600A

Bussman

AC500 V, 1600 A