Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 246

Advertising
background image

HOA Keypad Display

Fault Name

HISUC

High Suction

High Section Pressure

Cause

Possible Solution

The suction pressure has fallen below the

level set in Q5-12 for longer than the time

set in Q5-13. This is only effective when

Q5-14, High Suction Pressure Behavior

Select is set to 2 (fault).

• Reduce the system pressure.
• Set the High Suction Pressure fault characteristics in Q5-12, Q5-13, and Q5-18.
• Drive response to this condition is controlled by Q5-14, High Suction Pressure Behavior Select.
• Auto-restart of this fault is controlled by Q5-14, High Suction Pressure Behavior Select and Q5-15, Suction

Pressure Auto-restart Time.

HOA Keypad Display

Fault Name

HWL

High Water Level
The “High Water Level” digital input is active (H1-0o = 90).

Cause

Possible Solution

The Low Water Level switch is activated or

P1-31, High Water Digital Input

Configuration, is programmed incorrectly.

Lower the water level and/or adjust the High Water Level switch.

HOA Keypad Display

Fault Name

LF

Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.

Cause

Possible Solution

The output cable is disconnected

• Check for wiring errors and properly connect the output cable.
• Correct the wiring.

The motor winding is damaged

• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.

The output terminal is loose

• Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Main Circuit Wire

Gauges and Tightening Torque on page 134

for details.

The rated current of the motor being used

is less than 5% of the drive rated current

Check the drive and motor capacities.

An output transistor is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

A single-phase motor is being used

The drive cannot operate a single phase motor.

HOA Keypad Display

Fault Name

LF3

<1>

Power Unit Output Phase Loss 3
• Phase loss occurred on the output side
• Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection

Cause

Possible Solution

The gate drive board in the power unit is

damaged.

Cycle the power supply. If the fault continues to occur, replace the gate drive board or the drive. Contact

Yaskawa or a Yaskawa representative for instructions on replacing the gate drive board.

Cable to the current detection circuit in the

power unit is damaged or not connected

properly.

Check for incorrect wiring and correct any wiring mistakes.

Cable between the output rector and the

power unit is loose or not connected.

Contact Yaskawa or your nearest sales representative for instructions.

<1> Detected in models 4A0930 and 4A1200.

HOA Keypad Display

Fault Name

LFB

Low Feedback
The feedback signal is too low.

Cause

Possible Solution

5.2 Fault Detection

246

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide