No.

Parameter Name

Setting Range

Default

P5-02

HAND Reference 1

0.0 to E1-04

40.0 Hz

n

P5-04: HAND Key Function Selection

Selects whether the HAND key on the HOA keypad is active. Disabling this function by setting P5-04 to 0 will prevent the

drive from entering HAND Mode.

No.

Parameter Name

Setting Range

Default

P5-04

HAND Key Function Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

n

Q1-01: PID Controller Setpoint 1

Sets the PID setpoint for the controller. The drive will use the system feedback signal and modulate the pump speed to regulate

the feedback at the Q1-01 setpoint. The units for Q1-01 are selected by b1-01 and the scaling is set in parameter P1-03. This

parameter is active when b1-01 (Reference Source) is set to 0 (HOA keypad).

No.

Parameter Name

Setting Range

Default

Q1-01

PID Controller Setpoint 1

0.0 to 6000.0

0.0 PSI

n

Q5-03: Suction Pressure Setpoint

Sets the Suction Pressure setpoint. The units of Q5-03 are selected in Q5-01 and the scaling is set in Q5-02 (Suction Transducer

Scaling). The Suction Pressure function is enabled by setting Q5-01 = 1 (Suction Pressure). This function uses Q5-03 as the

setpoint instead of Q1-01, and Q5-02 as the feedback scaling instead of P1-02. Set b5-01 to a value other than 0 to enable the

drive PID controller and use this function.
This feature can be used to allow the drive to control (outlet) pressure when there is adequate pressure on the inlet side of the

pump by setting Q5-01 to 1 (Suction Pressure). When the suction pressure (pump inlet pressure) drops to the Suction Pressure

Setpoint (Q5-03), it will regulate the suction pressure and the outlet pressure will be allowed to drop. This requires both a

suction pressure transducer on the pump inlet and a pressure feedback transducer on the pump output.

No.

Parameter Name

Setting Range

Default

Q5-03

Suction Pressure Setpoint

0.0 to 1200.0

20.0 PSI

n

Q5-06: Wake-Up Suction Pressure

Sets the wake up level for the suction pressure control function. The drive falls asleep based on the Q5-04 level and Q5-05

delay time. The drive will wake up when the suction pressure feedback rises above the Q5-06 setting for the time set in Q5-07

AND the standard sleep function calls for a wake up (P1-04 and P1-05).

No.

Parameter Name

Setting Range

Default

Q5-06

Wake-Up Suction Pressure

0.0 to 1200.0

30.0 PSI

n

Q5-09: Low Suction Pressure Detection Level

Sets the level at which a Low Suction Pressure alarm or fault will occur. When the suction pressure feedback falls below the

Q5-09 setting for the time set in Q5-10, the drive will respond based on the setting in Q5-11.

No.

Parameter Name

Setting Range

Default

Q5-09

Low Suction Pressure Detection Level

0.0 to 1200.0

0.0 PSI

n

Q5-10: Low Suction Pressure Detection Time

Sets the delay time after which a Low Suction Pressure alarm or fault will occur. When the suction pressure feedback falls

below the Q5-09 setting for the time set in Q5-10, the drive will respond based on the setting in Q5-11.

No.

Parameter Name

Setting Range

Default

Q5-10

Low Suction Pressure Detection Time

0.0 to 300.0

0.1 min

4.6 Basic iQpump Setup and Application Preset Parameters

234

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide