No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S3-03

(321C) Secondary PI Display

Digits

PI2 UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2. 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

Sets the decimal place display for secondary PI units.

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 2

Range: 0 to 3

S3-04

(321D) Secondary PI Unit

Selection

PI2 Unit Sel

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: LPM

13: CMM

14: No unit

15: %

0: Inch of water (WC)

1: Pounds per square inch (PSI)

2: Gallons per minute (GPM)

3: Degrees Fahrenheit (F)

4: Cubic feet per minute (CFM)

5: Cubic meters per hour (CMH)

6: Liters per hour (LPH)

7: Liters per second (LPS)

8: Bar (Bar)

9: Pascals (Pa)

10: Degrees Celsius (C)

11: Meters (Mtr) (Ft: Feet)

12: Liters per minute (LPM)

13: Cubic meters per minute (CMM)

14: No unit

15: Percentage (%)

Default: 15

Range: 0 to 15

S3-05

(321E) Secondary PI Setpoint

Value

PI2 Setpoint

Sets the secondary PI controller target value.

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-06

(321F)

Secondary PI

Proportional Gain

Setting

PI2 Gain

Sets the proportional gain of the secondary PI controller. A

setting of 0.00 disables P control.

Default: 1.00

Min.: 0.00

Max.: 25.00

S3-07

(3220)

Secondary PI Integral

Time Setting

PI2 I Time

Sets the integral time for the secondary PI controller. A setting

of 0.0 s disables integral control.

Default: 1.0 s

Min.: 0.0

Max.: 360.0

S3-08

(3221)

Secondary PI Integral

Limit Setting

PI2 I Limit

Sets the maximum output possible from the integrator.

Default: 100.0%

Min.: 0.0

Max.: 100.0

S3-09

(3222)

Secondary PI Output

Upper Limit

PI2 Upper Limit

Sets the maximum output possible from the secondary PI

controller.

Default: 100.0%

Min.: 0.0

Max.: 100.0

S3-10

(3223)

Secondary PI Output

Lower Limit

PI2 Lower Lim

Sets the minimum output possible from the secondary PI

controller.

Default: 0.00%

Min.: -100.00

Max.: 100.00

S3-11

(3224)

Secondary PI Output

Level Selection

PI2 Out Lvl Sel

0: Direct Acting

1: Inverse Acting

Sets the secondary PI controller output direction.

0: Normal Output (direct acting)

1: Inverse Output (inverse acting)

Default: 0

Range: 0, 1

S3-12

(3225)

Secondary PI Disable

Mode

PI2 Disable Mode

0: No output

1: Lower Limit (S3-10)

2: Setpoint

Selects the secondary PI controller output when disabled.

0: No output (0%)

1: Lower Limit (S3-10)

2: Setpoint

Default: 0

Range: 0 to 2

S3-13

(3226)

Secondary PI Low

Feedback Detection

Level

PI2 Low FB Lvl

Sets the secondary PI low feedback detection level.

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-14

(3227)

Secondary PI Low

Feedback Detection

Time

PI2 Low FB Time

Sets the secondary PI low feedback detection delay time in

seconds.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

S3-15

(3228)

Secondary PI High

Feedback Level

PI2 High FB Lvl

Sets the secondary PI high feedback detection level.

Default: 100.00

<1>

Min.: 0.00
Max.: 600.00

<2>

B.13 S: Special Application

398