Figure 4.39, Illustrates how gain and bias settings work, L5-01: number of auto restart attempts – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 222

Advertising
background image

Terminal AM

1.

View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-04 will be output from terminal AM.

2.

Adjust H4-05 viewing the monitor connected to the terminal AM.

3.

View the value set to H4-06 on the digital operator; terminal AM will output a voltage equal to 0% of the parameter

being set in H4-04.

4.

Adjust H4-06 viewing the output signal on the terminal AM.

Output Voltage

Output Voltage

0 V

5 V

10 V

Gain 150%
Bias 0%

Gain = 150%
Bias = 0%

Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%

Gain 100%
Bias 0%

Gain 50%
Bias 0%

100%

Monitor Value

Monitor Value

0%

H4-07, 08 = 0

H4-07, 08 = 1

10 V

-10 V

100%

5 V

15 V

-5 V

-15 V

-100%

Figure 4.39 Analog Output Gain and Bias Setting Example 1 and 2

Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.

Gain = 100%
Bias = 30%

Gain = 100%
Bias = 0%

Gain 100%

Bias 30%

Gain 100%

Bias 0%

Monitor Value

Monitor Value

0 V

3 V

10 V

100%

0%

Output Voltage

Output Voltage

H4-07, 08 = 0

H4-07, 08 = 1

10V

-10 V

100%

3 V

-4 V

-100%

Figure 4.40 Analog Output Gain and Bias Setting Example 3

n

H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection

Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters

H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.

Refer to Terminal AM/FM Signal

Selection on page 152

for details on setting S5.

No.

Name

Setting Range

Default

H4-07

Multi-Function Analog Output Terminal FM

Signal Level Selection

0 to 2

0

H4-08

Multi-Function Analog Output Terminal AM

Signal Level Selection

0 to 2

0

Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA

n

L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.
When the counter reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.

4.6 Basic iQpump Setup and Application Preset Parameters

222

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide