Iqpump model identification and mounting, Connect motor and line power, Real-time clock setup – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 4

Advertising
background image

Step

1

iQpump Model

Identification and Mounting

To make sure you received the correct model, it is

essential to verify the iQpump nameplate with your order

and make sure the iQpump has the correct rating so it can

be used with your motor. Please check the nameplate

information as shown in the example below.

• Check that the available power will meet the input

power requirements.

• Ensure that the output power from the iQpump is

compatible with the motor requirements.

Mounting the iQpump

• In the case of systems with more than one iQpump, follow

the above procedure for each iQpump and motor.

The mounting of the iQpump is extremely important
regarding environment and accessibility. Depending on your
system, there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; Refer to the iQpump1000
Quick Start Guide (Document No. TOEPYAIP1W01)

received with the iQpump, Section 2.2 Mechanical
Installation
. Match the model that you received and follow
the procedure described in the manual to ensure a safe and
functional installation. In cases where the system has more
than one iQpump, refer to the proper clearances required for
adequate ventilation. Please pay particular attention to:

• The clearances to be maintained around the enclosure

for adequate ventilation.

• The environmental specifications such as avoiding

excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.

Removing and Attaching the Terminal Cover

Improper removal of the iQpump terminal cover as well as
front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention

Open Chassis

NEMA 1

Drive Model

Number

Input Power

Rating

Output

Power
Rating

Serial

Number

UL File

Number

Drive Spec Number

Weight

Software

Version

Normal

Duty Amps

CIMR-PW2A0021FAA

CIMR-PW2A0021FAA

CC :

8000

6W3050 - 2 - 100
J0073D207410100

to the iQpump1000 Quick Start Guide TOEPYAIP1W01
Section 3.5 Removing and Attaching the Terminal Cover.

Connect Motor and

Line Power

Step

2

WARNING DO NOT CONNECT ANY OF THE

FOLLOWING TERMINALS TO EARTH GROUND

B1

B2

-

+1

+2

+3

NOT USED

Fig.1 & 2 below show the electrical connections for the input
power and motor terminals for various iQpump models. Select
the proper diagram for the model you are installing (see Step
1).
WITH POWER OFF make the appropriate connections.
Make sure to follow good wiring practices and all
applicable codes. Ensure that the equipment is grounded
properly as shown in fig. 1

DANGER; LETHAL VOLTAGES ARE PRESENT - Before
applying power to the iQpump, ensure that the terminal
cover is fastened and all wiring connections are secure.
After the power has been turned OFF, wait at least five
minutes until the charge indicator extinguishes
completely before touching any wiring, circuit boards or
components.

!

Make sure the iQpump has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be
equal to or greater than the motor rated voltage.

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

To change direction of motor
rotation swap any two of the

three motor leads.

Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2_0110 & Larger and 4_0058 & Larger

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis

ground

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

Use L1, L2 for

1Ø Input Power *

BUS TERMINALS:
DO NOT CONNECT TO GROUND

Use L1, L2, L3 for

3Ø Input Power

To change
direction of

motor rotation
swap any two

of the three

motor leads.

Fig. 1 Input Power and Output Motor Electrical Connections for
Models:
2_0004 - 2_0056, 4_0002 - 4_0044 and 5_0003 - 50011

Use L1, L2 for

1Ø Input Power

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

L1 L2 L3

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis ground

*

DC Bus terminals
location varies by

model.

*

Step

3

Real-time

Clock Setup

This step shows how to setup the
iQpump real-time clock for first
use.

Note:

If clock is not set the drive

can still be programmed and
operated, but ALM light will flash
every 30s and showing Clock
Not Set
message.

Power up the drive and set the

real-time Clock. The real-time

Clock setup screen will appear at

first power up.

Press to set the clock.

Note:

After the real-time clock is

set the real-time clock setup
screen will not show again unless
parameter o4-17 is set to “Set”.

Real-time Clock Setup Screen

Use to move cursor to

The left and to move

cursor to the right

use to adjust.

When date and time are set

press to save.

Note:

Do NOT adjust sec per

month.

Example:

Jun 12

th

2012, 7:35am

4

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide