P8: de-scale / de-ragging, P9: network options – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 385

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P7-08

(0D98) Anti-Jam Release Time AJ Release Time

Sets the length of time that the current must fall below the level

set in P7-03 to resume normal operation.

Default: 2.0 s

Min.: 0.5

Max.: 10.0

u

P8: De-Scale / De-Ragging

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P8-01

(0DB0)

<1>

De-scale Operation

Selection

De-scale Sel

Selects de-scale functionality.

0: Disabled

1: De-scale Enabled

2: Force De-scale

Default: 0

Range: 0 to 2

P8-02

(0DB1)

<1>

De-scale Cycle Count

De-scale Cycles

Sets the maximum number of cycles attempted before the Anti-

Jam fault occurs. Also sets the number of fwd/rev cycles for the

De-scale function.

Default: 1

Min.: 1

Max.: 100

P8-03

(0DB2)

<1>

De-scale Frequency

Reference

De-scale FreqRef

Sets the speed during the de-scale operation.

Default: 25.00

Hz

Min.: 0.00

Max.: 400.00

P8-04

(0DB3)

<1>

De-scale Forward Run

Time

De-scale FWD Run

Sets the amount of time the drive will run in the forward

direction each cycle during the de-scale function.

Default: 10 s

Min.: 1

Max.: 6000

P8-05

(0DB4)

<1>

De-scale Reverse Run

Time

De-scale REV Run

Sets the amount of time the drive will run in the reverse direction

each cycle during the de-scale function.

Default: 10 s

Min.: 1

Max.: 6000

P8-06

(0DB5)

<1>

De-scale Acceleration

Time

De-scale Accel

Sets the amount of time it will take the drive to accelerate from

zero to the De-scale frequency reference P8-03.

Default: 2.0 s

Min.: 0.0

Max.: 600.0

P8-07

(0DB6)

<1>

De-scale Deceleration

Time

De-scale Decel

Sets the amount of time it will take the drive to decelerate from

the De-scale frequency reference P8-03 to zero.

Default: 2.0 s

Min.: 0.0

Max.: 600.0

P8-08

(0DB7)

<1>

De-scale Pump Run

Time

De-Scale Time

Sets the number of pump operating hours (pump speed > 0)

before a de-scale routine will run.

Default: 168.0 H

Min.: 0.1

Max.: 2000.0

<1> Available in drive software versions PRG: 8551 and later.

u

P9: Network Options

Parameters in this group are functional only when P1-01, Pump Mode, is set to 3 (MEMOBUS network).

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

P9-01

(0DF4) Lead Drive Selection

Lead Drive Sel

0: Next Available

1: Lowest Runtime

2: Stop History

Specifies how the next lead drive is selected.

0: Next available

1: Lowest runtime

2: Stop history

Default: 1

Range: 0 to 2

P9-02

(0DF5) Feedback Source

Feedback Source

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

Defines which signal to use for PI feedback when P1-01, Pump

Mode, is set to 3 (MEMOBUS network).

0: Analog only

1: Ana->Net, No Alrm

2: Ana->Net, Alarm

3: Network only

Default: 0

Range: 0 to 3

P9-03

(0DF6) Alternation Time

Alternation Time

Specifies the time for a drive to request alternation.

Setting this parameter to 0 disables the function.

Default: 24 H

Min.: 0

Max.: 1000

B.11 P: Pump Parameters