4.4 Pump Application Presets

The following sections list the parameters affected by the different Application Presets.

Note:

Setting A1-03 to 6011 (VTC Pressure Control) changes the Quick Start and Pre-set parameters (tables below) and also changes HAND

Mode so that it is no longer lower-limited by the minimum pump frequency or the thrust frequency. Also, the default for P1-06 when in

RPM mode is 1800 RPM instead of 2400 RPM.

u

Parameters Set Depending on A1-03 Setting

The following table shows the parameters that are set depending on the A1-03 initialization:

A1-03 = 6008

(A1-06 = 8)

Pressure Control

A1-03 = 6009

(A1-06 = 9)

Pump Down Level

A1-03 = 6010

(A1-06 = 10)

Geothermal Mode

A1-03 = 6011

(A1-06 = 11)

VTC Pressure Ctl

A1-03 = 7770

(A1-06 = 1)

General Purpose

A1-03 = 7771

(A1-06 = 2)

Sub Mtr GP Oper

Parameter

Value

Parameter

Value

Parameter

Value

Parameter

Value

Parameter

Value

Parameter

Value

b5-09

1

b1-01

5

b5-03

5.0

b1-01

1

A1-02

0

b5-39

2

b5-01

0

C1-01

15.0 sec

b1-02

1

b5-01

0

P1-02

6

H3-10

21

C1-02

15.0 sec

b5-01

0

H1-06

4

P2-01

2

o1-08

180

E2-04

4

C1-01

25.0 sec

H1-07

0

P2-23

0.00%

L5-01

0

C1-02

25.0 sec

H2-01

0

P1-03

100.0 PSI

H1-06

4

H2-02

A

P1-06

35.0 Hz

H1-07

F

o1-06

0

P2-03

15 sec

H2-01

0

P1-05

0 sec

P2-23

0.00%

H2-02

A

d1-01

40.00 Hz

P3-50

35.0 Hz

H3-10

2

P3-60

35.0 Hz

L5-01

0

P3-70

35.0 Hz

L5-04

180.0 sec

P4-12

0.0 Hz

o1-06

0

P5-02

6.0 Hz

P1-05

0 sec

Q5-03

40.0 PSI

P1-06

0.0 Hz

Q5-06

50.0 PSI

P4-12

0.0 Hz

Q5-09

20.0 PSI

P4-17

0.0 min

Q5-10

5.0 min

P5-02

0.0 Hz

Q5-11

2

Q5-16

1.00

Q5-17

3.0 sec

H2-01

80H

H2-02

81H

H2-03

82H

P3-01

2

P3-04

5.0 PSI

P3-06

5.0 Hz

P3-07

7.0 sec

P3-10

2.0 PSI

4.4 Pump Application Presets

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

169