Internal cooling fan has malfunctioned

• Cycle power to the drive.
• Check for fan operation.
• Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation

time of the fan maintenance timer with U4-04.

• If the cooling fan has exceeded its expected performance life or is damaged in any other way, follow the

replacement instructions in the

Peripheral Devices & Options

chapter.

Fault detected in the internal cooling fan or

magnetic contactor to the power supply.

• Cycle power to the drive.
• If the fault continues to occur, replace the power board/gate drive board or the entire drive.
• Contact Yaskawa or a Yaskawa representative for instructions on replacing the power board/gate drive

board.

HOA Keypad Display

Fault Name

FDBKL Wire Break

PID Feedback Loss
The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA.

Cause

Possible Solution

The analog input programmed for PID

feedback loss has risen above 21 mA or

fallen below 3 mA. This is effective only

when b5-12 Feedback Loss 4 to 20 mA

Detection Selection is set to 2 (fault).

• Confirm that the PID feedback source is installed and working properly.
• Drive response to this condition is controlled by b5-12, Feedback Loss 4 to 20 mA Detection Selection

and b5-13, Feedback Loss Go To Frequency.

• Auto-restart of this fault is controlled by L5-42, Feedback Loss Fault Retry Selection.

HOA Keypad Display

Fault Name

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

Cause

Possible Solution

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

A damaged motor cable is creating a short

circuit

• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.

Excessive leakage current at the drive

output

• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.

The drive started to run during a current

offset fault or while coasting to a stop

• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

HOA Keypad Display

Fault Name

HFB

High Feedback
The feedback signal is too high.

Cause

Possible Solution

The feedback signal has risen above the

level set in P1-11, High Feedback Level,

for the time set in P1-12, High Feedback

Level Fault Delay Time.

This is effective only when P1-13, High

Feedback Selection, is set to 0 (Fault and

digital outt).

• Set the High Feedback fault characteristics in P1-11 and P1-12.
• Drive response to this condition is controlled by P1-13, High Feedback Selection. Auto-restart of this fault

is controlled by L5-41, High Feedback Fault Retry Selection.

HOA Keypad Display

Fault Name

HIFLO

High Flow

High Flow
The meter has detected a high flow condition.

Cause

Possible Solution

The flow is too high

Reduce the flow

The measured water flow has risen above

the P6-17 level for the time set in P6-18.

This is only effective when P6-19, High

Flow Select is set to 2 (fault).

• Set the High Flow fault characteristics in P6-17 and P6-18.
• Drive response to this condition is controlled by P6-19, High Flow Select.
• Auto-restart of this fault is controlled by P6-19, High Flow Select.